INSTALLATION, COMMISSIONING, AND MAINTENANCE MANUAL
REVISION 1.01 MAR 2021 - P/N 30-NPWICM-000
52
3.10.4. Electrical Connection.
Refer to
Figure 33.
DANGER
Failure to follow
ELECTRICAL CONNECTION
instructions correctly can result in
ELECTROCUTION
!
Figure 33
Electrical Connection
Corrosion Monitor Assembly Model CMA-1
(a)
Remove cover by removing tamper resistant screw.
(b)
Run wires through an approved raceway and conduit connector and affix the connector on the device. Two
knockouts are provided on the pressure switch for ½” conduit. Individual switch compartments and ground screws
are suitable for dissimilar voltage.
(c)
Connect wires to the appropriate terminal connections shown in
Figure 32.
Switch contacts are SPDT; 10 Amps
@ 125/250 VAC, 2 Amps @ 30 VDC.