UNITED FIRE SYSTEMS
NITROGEN-
PAC™
MODEL SC-W
INSTALLATION, COMMISSIONING, AND MAINTENANCE MANUAL
REVISION 1.01 MAR 2021 - P/N 30-NPWICM-000
35
3.2.4. Outlet Connection.
Refer to
Figure 20.
Figure 20
Outlet Connection
(a)
Remove and discard plastic plug from Model SC-W assembly outlet port.
(b)
Attach outlet valve assembly to Model SC-W assembly outlet port. Tighten securely, but do not overtighten.
(c)
Orient outlet valve assembly with outlet fitting pointed downward.
(d)
Retain the outlet hose for attachment of nitrogen piping to outlet.
IMPORTANT
DO NOT omit the provided outlet hose. The hose minimizes compressor motor vibration from reaching the nitrogen
piping.
SEE (a) BELOW
SEE (b) BELOW
SEE (c) BELOW
SEE (d) BELOW