40
3.3. Piping Requirements.
All piping should be Sch. 40 black steel. All fittings should be Class 150 black threaded.
Galvanized pipe is not recommended. All pipe should be securely fastened in a workmanlike manner. Limit the pipe
lengths between the Model SC-W assembly and the sprinkler valve(s) to those in
Table 7
.
Table 7
Piping Limitations
SINGLE RISER SYSTEM
CHOOSE ONE
OPTION
Pipe Size (NPS)
Maximum Length
– All Pipe
(feet)
OPTION 1
Supply Pipe from Model SC-W to sprinkler valve = 1/2 inch
300
OPTION 2
Supply Pipe from Model SC-W to sprinkler valve = 3/4 inch
600
TWO RISER SYSTEM
CHOOSE ONE
OPTION
Pipe Size (NPS)
Maximum Length
– All Pipe
(feet)
OPTION 1
Supply Pipe from Model SC-W to Branch Pipes = 1/2 inch
300
Branch Pipes from Supply Pipe to sprinkler valve = 1/2 inch
OPTION 2
Supply Pipe from Model SC-W to Branch Pipes = 3/4 inch
600
Branch Pipes from Supply Pipe to sprinkler valve = 1/2 inch
NOTE:
On multiple riser systems, branch pipes from supply pipe to AMDs should be as short as possible.