For the low pressure dual-pump motors for 30RQM/30RQP 160-520 units (option 116U)
No.
(2)
Description
(3)
Units
30RQM/30RQP
160 180 210 230 240 270 310 330 380 430 470 520
1
Nominal efficiency at full load and nominal voltage
%
85,9 86,4 87,5 87,5 87,5 87,5 87,5 89,6 89,6 89,6 89,7 89,7
Nominal efficiency at 75% full load and nominal voltage
%
86,4 86,9 88,2 88,2 88,2 88,2 88,2 90,4 90,4 90,4 90,0 90,0
Nominal efficiency at 50% full load and nominal voltage
%
84,9 85,7 87,5 87,5 87,5 87,5 87,5 89,9 89,9 89,9 89,0 89,0
2
Efficiency level
-
IE3
3 Year of manufacture
-
This information varies depending on the manufacturer and model
at the time of incorporation. Please refer to the motor nameplates.
4
Manufacturer’s name or trademark, commercial registration
number and registered address
-
Same as above
5
Product’s model number
-
Same as above
6
Number of motor poles
-
2
2
2
2
2
2
2
2
2
2
2
2
7-1
Nominal shaft power output at full load and nominal voltage
(400 V)
kW
1,5 2,2
3
3
3
3
3
4
4
4
5,5
5,5
7-2
Maximum input power (400 V)
(5)
kW
1,94 2,80
3,81 3,81 3,81 3,81 3,81
4,96 4,96 4,96 6,80 6,80
8
Nominal input frequency
Hz
50
50
50
50
50
50
50
50
50
50
50
50
9-1 Nominal voltage
V
3 x 400
9-2
Maximum current drawn (400 V)
(6)
A
3,41
4,92 6,81 6,81 6,81 6,81 6,81 8,27 8,27 8,27
11,30 11,30
10
Nominal speed
r/s - r/min
48 - 2900
11
Product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(4)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in
the specific conditions in the Carrier selection programs.
IV - Potentially explosive atmospheres
-
Non ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
(5) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(6) To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current
draw.
For the high pressure single and dual-pump motors for 30RQM/30RQP 160-520 units (options 116R and 116V)
No.
(2)
Description
(3)
Units
30RQM/30RQP
160 180 210 230 240 270 310 330 380 430
470
520
1
Nominal efficiency at full load and nominal voltage
%
87,5 87,5 89,6 89,6 89,6 89,7 89,7 89,7 89,7 90,8 90,8 90,8
Nominal efficiency at 75% full load and nominal voltage
%
88,2 88,2 90,4 90,4 90,4 90,0 90,0 90,0 90,0 90,8 90,8 90,8
Nominal efficiency at 50% full load and nominal voltage
%
87,5 87,5 89,9 89,9 89,9 89,0 89,0 89,0 89,0 89,6 89,6 89,6
2
Efficiency level
-
IE3
3 Year of manufacture
-
This information varies depending on the manufacturer and model at the
time of incorporation. Please refer to the motor nameplates.
4
Manufacturer’s name or trademark, commercial
registration number and registered address
-
Same as above
5
Product’s model number
-
Same as above
6
Number of motor poles
-
2
2
2
2
2
2
2
2
2
2
2
2
7-1
Nominal shaft power output at full load and nominal
voltage (400 V)
kW
3
3
4
4
4
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7-2
Maximum input power (400 V)
(5)
kW
3,81 3,81
4,96 4,96 4,96 6,80 6,80 6,80 6,80 9,16 9,16 9,16
8
Nominal input frequency
Hz
50
50
50
50
50
50
50
50
50
50
50
50
9-1 Nominal voltage
V
3 x 400
9-2
Maximum current drawn (400 V)
(6)
A
6,81 6,81 8,27 8,27 8,27
11,30 11,30 11,30 11,30 15,30 15,30 15,30
10
Nominal speed
r/s - r/min
48 - 2900
11
Product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(4)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the
specific conditions in the Carrier selection programs.
IV - Potentially explosive atmospheres
-
Non ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
(5) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(6) To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current
draw.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30RQM AND 30RQP UNITS
20
Summary of Contents for Carrier 30RQM 160
Page 63: ......