4.3 -
Electrical data 30RQM 160-520
30RQM
160
180
210
230
240
270
310
330
380
430
470
520
Power circuit
Nominal voltage
V-ph-Hz
400 - 3 - 50
Voltage range
V
360 - 440
Control circuit supply
24 V via internal transformer
Nominal unit current draw
(1)
Circuit A&B
A
100
110
133
147
151
166
191
199
233
266
294
322
Maximum unit input power
(2)
Circuit A&B
kW
80
88
107
118
120
134
152
161
188
215
236
258
Cosine Phi unit at maximum power
(2)
0,88 0,87 0,88 0,88 0,87 0,88 0,87 0,88 0,88 0,88 0,88 0,88
Maximum unit current draw (Un-10%)
(3)
Circuit A&B
A
144
158
192
211
215
241
273
289
337
385
422
460
Maximum unit current draw (Un)
(4)
Circuit A&B - Standard Unit
A
133
146
177
195
199
222
252
266
310
354
390
425
Circuit A&B - Unit with option 231
A
100
110
133
148
151
166
192
200
233
266
296
326
Maximum start-up current, standard unit (Un)
(5)
Circuit A&B
A
307
356
352
406
409
396
462
440
485
529
600
636
Max. start-up current, unit with soft starter (Un)
(5)
Circuit A&B
A
261
283
305
332
336
350
389
394
438
482
527
562
(1) Conditions equivalent to the standardised Eurovent conditions (evaporator water input-output temperature = 12 °C/7 °C, outside air temperature = 35 °C).
(2) Power input, compressors and fans, at the unit operating limits (saturated suction temperature 15 °C, saturated condensing temperature 68.3 °C) and nominal voltage
of 400 V (data given on the unit nameplate).
(3) Maximum unit operating current at maximum unit power input and at 360 V.
(4) Maximum unit operating current at maximum unit power input and at 400 V (values given on the unit nameplate).
(5) Maximum instantaneous starting current at operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of
the largest compressor).
Fan motor electrical data reported upstream of the variable drive at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: Current 3.8
A; Start-up current 20 A; Power input: 1.75 kW.
4.4 -
Electrical data 30RQP 160-520
30RQP
160
180
210
230
240
270
310
330
380
430
470
520
Power circuit
Nominal voltage
V-ph-Hz
400 - 3 - 50
Voltage range
V
360 - 440
Control circuit supply
24 V via internal transformer
Nominal unit current draw
(1)
Circuit A&B
A
97
107
130
144
147
162
186
195
227
260
288
316
Cosine Phi unit at maximum power
(2)
Circuit A&B
kW
81
88
108
118
120
134
153
161
188
215
237
259
Cosinus Phi unité à puissance maximale
(2)
0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88
Maximum unit current draw (Un-10%)
(3)
Circuit A&B
A
142
154
189
208
211
237
268
284
331
378
416
454
Maximum unit current draw (Un)
(4)
Circuit A&B - Standard Unit
A
131
142
174
192
195
218
247
261
305
348
383
419
Circuit A&B - Unit with option 231
A
98
108
131
146
148
164
188
197
230
262
291
321
Maximum start-up current, standard unit (Un)
(5)
Circuit A&B
A
305
353
349
402
405
392
458
436
479
523
594
629
Max. start-up current, unit with soft starter (Un)
(5)
Circuit A&B
A
259
279
302
329
332
346
384
389
433
476
520
556
(1) Conditions equivalent to the standardised Eurovent conditions (evaporator water input-output temperature = 12 °C/7 °C, outside air temperature = 35 °C).
(2) Power input, compressors and fans, at the unit operating limits (saturated suction temperature 15 °C, saturated condensing temperature 68.3 °C) and nominal voltage
of 400 V (data given on the unit nameplate).
(3) Maximum unit operating current at maximum unit power input and at 360 V.
(4) Maximum unit operating current at maximum unit power input and at 400 V (values given on the unit nameplate).
(5) Maximum instantaneous starting current at operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of
the largest compressor).
Fan motor electrical data reported upstream of the variable drive at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: Current 3.8
A; Start-up current 20 A; Power input: 1.75 kW.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30RQM AND 30RQP UNITS