METHOD A -

 12” (304.8 mm) Clearance to Combustible Wall 

Member:  Using  a  minimum  thickness  3.5”  (89  mm)  brick 

and  a  5/8”  (15.9  mm)  minimum  wall  thickness  clay  liner, 

construct a wall pass-through. The clay liner must conform 

to ASTM C315 (Standard Specification for Clay Fire Linings) 

or its equivalent. Keep a minimum of 12” (304.8 mm) of brick 

masonry between the clay liner and wall combustibles. The 

clay liner shall run from the brick masonry outer surface to 

the inner surface of the chimney flue liner but not past the 

inner surface. Firmly grout or cement the clay liner in place 

to the chimney flue liner.

METHOD B - 

9” (228.6 mm) Clearance to Combustible Wall 

Member:  Using  a  6”  (152.4  mm)  inside  diameter,  listed, 

factory-built  Solid-Pak  chimney  section  with  insulation 

of  1”  (25.4  mm)  or  more,  build  a  wall  pass-through  with  a 

minimum 9” (228.6 mm) air space between the outer wall of 

the chimney length and wall combustibles. Use sheet metal 

supports  fastened  securely  to  wall  surfaces  on  all  sides, 

to  maintain  the  9”  (228.6  mm)  air  space.  When  fastening 

supports to chimney length, do not penetrate the chimney 

liner (the inside wall of the Solid-Pak chimney). The inner end 

of the Solid-Pak chimney section shall be flush with the inside 

of the masonry chimney flue, and sealed with a non-water 

soluble refractory cement. Use this cement to also seal to 

the brick masonry penetration.

METHOD C - 

6” (152.4 mm) Clearance to Combustible Wall 

Member: Starting with a minimum 24 gage (.024” [.61 mm]) 

6” (152.4 mm) metal chimney connector, and a minimum 

24 gage ventilated wall thimble which has two air channels 

of  1”  (25.4  mm)  each,  construct  a  wall  pass-through. 

There  shall  be  a  minimum  6”  (152.4  mm)  separation  area 

containing fiberglass insulation, from the outer surface of the 

wall thimble to wall combustibles. Support the wall thimble, 

and cover its opening with a 24-gage minimum sheet metal 

support.  Maintain  the  6”  (152.4  mm)  space.  There  should 

also be a support sized to fit and hold the metal chimney 

connector. See that the supports are fastened securely to 

wall surfaces on all sides. Make sure fasteners used to secure 

the  metal  chimney  connector  do  not  penetrate  chimney 

flue liner.

METHOD D - 

2” (50.8 mm) Clearance to Combustible Wall 

Member: Start with a solid-pak listed factory built chimney 

section at least 12” (304 mm) long, with insulation of 1” (25.4 

mm) or more, and an inside diameter of 8” (2 inches [51 mm] 

larger than the 6” [152.4 mm] chimney connector). Use this 

as a pass-through for a minimum 24-gauge single wall steel 

chimney connector. Keep solid-pak section concentric with 

and  spaced  1”  (25.4  mm)  off  the  chimney  connector  by 

way of sheet metal support plates at both ends of chimney 

section. Cover opening with and support chimney section 

on both sides with 24 gage minimum sheet metal supports. 

See that the supports are fastened securely to wall surfaces on all sides. Make sure fasteners used to secure 

chimney flue line do not penetrate the inner liner.

NOTES:

1.  Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the 

wall pass-through system and the chimney wall, to but not past the inner flue liner face.

2.  A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a 

floor, or ceiling.

COMBUSTIBLE WALL CHIMNEY CONNECTOR PASS-THROUGHS

Le dégagement minimum de la cheminée à la brique et les

matériaux combustibles est de 5 cm (2 po) (50,8 mm)

Le dégagement minimum de la cheminée à la brique et les

matériaux combustibles est de 5 cm (2 po) (50,8 mm)

30 cm (304,8 mm, 12 po)

minimum aux matériaux

combustibles

Cheminée en

maçonnerie

Conduit de cheminée

Doublage en

argile réfractaire

Conduit de

raccordement

Dégagement minimum

de 30 cm (12 po, 

304,8 mm)

des briques 

Conduit de cheminée

Conduit de

raccordement

Dégagement minimum

de 5 cm (9 po)

(228,6 mm)

Nonsoluble

refractory

cement

Supports de

tôle d'acier

Cheminée en maçonnerie

Longueur de cheminée

à égalité avec le conduit

de fumée intérieur

Utiliser des pièces

de cheminée

fabriquées pour

le fixer solidement

au raccordement.

V

ide d’air

Longueur de

cheminée

préfabriquée et

répertoriée, à

isolant solide.

Minimum Vide d’air

de 5 cm (9 po)

(228,6 mm)

Longueur de

cheminée préfabriquée

Cheminée en maçonnerie

Supports de

tôle d'acier

Conduit de cheminée

Conduit de

raccordement

Le dégagement minimum de la cheminée aux

supports en tôle d’acier et aux matériaux

combustibles est de 5 cm (2 po). (50,8 mm)

Deux canaux d’aération

de 2,5 cm (1 po)

chacun. (25,4 mm)

Deux canaux d’aération

de 2,5 cm (1 po)

chacun. (25,4 mm)

Fabriqués en

tôle d’acier

Le dégagement minimum de la cheminée

aux supports en tôle d’acier et aux matériaux

combustibles est de 5 cm (2 po). (50,8 mm)

Isolant de fibre de

verre d’un minimum

de 152,4 mm (6 po).

Conduit de

raccordement

Conduit de cheminée

Cheminée

en maçonnerie

Supports de

tôle d'acier

Conduit de

raccordement

Supports de

tôle d'acier

Vide d’air de 5 cm

(2 po) (50,8 mm)

Longueur de

la cheminée

Section de

cheminée

1 po. Vide d’air

de (25,4 mm) à

la longueur de

cheminée

Dégagement minimum

de 5 cm (2 po)

(50,8 mm)

All manuals and user guides at all-guides.com

Summary of Contents for Ashley AW2020E

Page 1: ...C S627 00 R2016 Mobile home approved U S ONLY U S Environmental Protection Agency Certified to comply with 2020 particulate emissions standards R Report Number F19 476 SAFETY NOTICE If this heater is...

Page 2: ...gle Wall or Double Wall Black or Blued Steel 2100 F 650 C Minimum Chimney Height 12 3 7 m Maximum Log Length 21 533 5 mm Dimensions Overall Depth x Width x Height AW2020E BL 21 x 27 x 31 4 534 mm x 68...

Page 3: ...weld tabs provided in the parts box FIREBRICK CONFIGURATION Replace the Firebrick as shown in the illustration 5 16 18 x 1 1 2 BOLT WASHER HEATER TOP GASKET WELD TAB Assembly Instructions TOOLS AND M...

Page 4: ...SHEN UP A FIRE IN THIS HEATER KEEP ALL SUCH LIQUIDS WELL AWAY FROM THE HEATER WHILE IT IS IN USE IN THE EVENT OF A CHIMNEY FIRE PUSH THE AIR CONTROL FULL CLOSED TO DEPRIVE THE FIRE OF OXYGEN CALL THE...

Page 5: ...305 305 F 22 22 559 559 D B A C E F E OUTSIDE COMBUSTION AIR Your wood stove is approved to be installed with an outside air intake 4FAK which is necessary for a mobile home This type of installation...

Page 6: ...STRUCTURE OF THE MOBILE HOME SECURING APPLIANCE S ON A PEDESTAL TO THE FLOOR Use the designated holes to secure the unit to the floor SECURING APPLIANCE S WITH LEGS TO THE FLOOR 1 The bracket engages...

Page 7: ...iance and chimney connector joints An uncontrollable burn or excessive temperature indicates an excessive draft CHIMNEY Your wood stove may be hooked up with a 6 factory built or masonry chimney If yo...

Page 8: ...anufacturer The chimney must be the required height above the roof or other obstructions for safety and proper draft operation MASONRY CHIMNEY Ensure that a masonry chimney meets the minimum standards...

Page 9: ...pass through for a minimum 24 gauge single wall steel chimney connector Keep solid pak section concentric with and spaced 1 25 4 mm off the chimney connector by way of sheet metal support plates at b...

Page 10: ...lerates the drying time A good indicator of if the wood is ready to burn is to check the piece ends If cracks are radiating in all directions from the center then the wood should be dry enough to burn...

Page 11: ...e door If the piece ignites within 90 seconds from the time it was placed into the stove your wood is correctly dried If ignition takes longer your wood is damp If your wood hisses and water or vapor...

Page 12: ...as lost energy Therefore efficiency calculated using the lower heating value of wood will be higher than the efficiency calculated using the higher heating value In the United States all woodstove eff...

Page 13: ...e between 275 F and 500 F Below these temperatures the build up of creosote is promoted Above 500 F heat is wasted since a too large quantity is lost into the atmosphere TO PREVENT CREOSOTE BUILD UP A...

Page 14: ...hould be washed only when cold PAINT Only clean your stove with a dry soft cloth that will not harm the paint finish If the paint becomes scratched or damaged it is possible to give your wood stove a...

Page 15: ...stal AW2020E BP 1 8 29065 Pedestal Front AW2020E BP 1 9 610922 Pedestal Weldment AW2020E BP 1 10 610925 Ashpan Housing AW2020E BL 1 11 40566 Cast Iron Leg AW2020E BL 4 12 29071 Ash Pan 1 13 891137 Bru...

Page 16: ...e 1 8 2 4 86952 Secondary Air Tube 11 64 1 5 29039 Brick Retainer left 1 6 29040 Brick Retainer right 1 7 40561 Ash Plug 1 8 24103A Half Pumice Firebrick 4 1 2 X 4 1 2 2 9 891414A Half Firebrick 2 10...

Page 17: ...Notes All manuals and user guides at all guides com...

Page 18: ...Notes All manuals and user guides at all guides com...

Page 19: ..._____ Engineer Name ________________________________ License No ____________________________________ Company _____________________________________ Telephone No _________________________________ Stove...

Page 20: ...VER CE GUIDE DANS UN ENDROIT S R DES FINS DE R F RENCE LORSQUE VOUS NOUS CRIVEZ VEUILLEZ INDIQUER LE NUM RO COMPLET DU MOD LE QUI FIGURE SUR LA PLAQUE SIGNAL TIQUE DE L APPAREIL DE CHAUFFAGE LORSQUE V...

Page 21: ...___ Service de 07 Date _____________________ Nom de l ing nieur ____________________________ N de licence _________________________________ Compagnie ___________________________________ N de t l phone...

Page 22: ...64 1 5 29039 retenue de brique gauche 1 6 29040 retenue de brique droite 1 7 40561 bouchon de cendre 1 8 24103A brique r fractaire demi pierre ponce 4 1 2 x 4 1 2 2 9 891414A demi brique r fractaire 2...

Page 23: ...r d air 1 4 891492 Ensemble ventilateur B36 1 5 26060 Bouclier arri re 1 6 610926 Cendrier arri re AW2020E BP 1 7 29068 Pi destal AW2020E BP 1 8 29065 Front de pi destal AW2020E BP 1 9 610922 Soudure...

Page 24: ...ar une neuve Effectuez la proc dure en sens inverse apr s remplacement Lors du remplacement de la vitre vous devrez changer le joint de la vitre pour vous assurer qu elle soit bien tanche Ne lavez jam...

Page 25: ...istres Attendez que le feu s teigne et que l appareil de chauffage refroidisse puis inspectez les dommages de la chemin e S il n y aucun dommage effectuez le nettoyage de la chemin e pour garantir qu...

Page 26: ...qu un bon feu est tabli un taux de combustion plus bas peut tre la meilleure option pour un chauffage efficace Un taux de combustion plus bas ralentit la sortie du flux de chaleur utilisable hors de l...

Page 27: ...glementations f d rales LES PREMIERS FEUX La peinture fra che de votre po le a besoin d tre cuite pour pr server sa qualit Une fois que le combustible est correctement allum faites uniquement br ler d...

Page 28: ...pour vous assurer que la temp rature ne d passe jamais 246 C 475 F sur un thermom tre magn tique pour une installation sur des tuyaux de po le paroi simple ou 482 C 900 F sur sonde thermom trique pour...

Page 29: ...in e Solid Pak fabriqu e en usine agr e d au moins 12 304 mm de diam tre int rieur avec une isolation de 1 25 4 mm ou plus et un raccord de chemin e de 8 de diam tre int rieur de 2 pouces 51 mm plus g...

Page 30: ...N MA ONNERIE Assurez vous qu une chemin e en ma onnerie r ponde aux standards minimum de l Association nationale de protection contre les incendies NFPA en la faisant inspecter par un professionnel As...

Page 31: ...t avoir le m me diam tre que la sortie du po le 6 po Si ce n est pas le cas nous vous recommandons de contacter votre vendeur afin de vous assurer qu il n y aura aucun probl me de tirage Le tuyau de p...

Page 32: ...l y ait ou non des mati res combustibles 2 Les appareils foyer existants au sein du domicile tels que des chemin es ou d autres appareils de chauffage mettent des odeurs ne fonctionnent pas correcteme...

Page 33: ...libre entre le tuyau et le plafond Il doit galement y avoir une protection du sol sous la conduite horizontale qui s tend de 2 po au del de chaque c t du conduit de chemin e La hauteur entre le sol et...

Page 34: ...D MARRER OU RAVIVER UN FEU DANS CE PO LE MAINTENEZ TOUS CES LIQUIDES LOIGN S DU PO LE EN CAS D INCENDIE DE CHEMIN E FERMEZ COMPL TEMENT LA COMMANDE D AIR AFIN DE PRIVER LE FEU D OXYG NE APPELEZ LES P...

Page 35: ...le de la chemin e 12 3 7 m Longueur maximale des b ches 21 po 533 5 mm Dimensions G n rales Profondeur x Largeur x Hauteur AW2020E BL 21 po x 27 po x 31 4 po 534 mm x 686 mm x 798 mm AW2020E BP 21 po...

Page 36: ...e chauffage Contactez les responsables locaux de l immeuble ou des services d incendie pour conna tre les permis restrictions et exigences d installation dans votre r gion MISE EN GARDE Veuillez lire...

Reviews: