UT-102

UNIVERSAL PROCESS INDICATOR & CONTROLLER

8

Continue Configuration Mode

 

Range / Values

Parameter

nadd
0001

NODE ADDRESS [COMMUNICATION]

Device Address for Communication

Display

Increase the no. by        key, decrease by        key.

Range  :  Values between 

0001

 to 

0127

Default Value  :  

0001

:  Baud Rate 4800

4800

:  Baud Rate 9600

9600

:  Baud Rate 19200

19.2k

Change value by        key, or by        key.

baud
9600

BAUD RATE [COMMUNICATION]

Baud Rate  for Communication

Values  :  

Default Value  :  

9600

NOTE :

 Applicable if Communication Output.

NOTE :

 Applicable if Communication Output.

:  Even Parity

EvEn

:  Odd Parity

Odd

:  None Parity

none

Change value by        key, or by        key.

pr1t
none

PARITY [COMMUNICATION]

Parity check for Communication

Values  :  

Default Value  :  

none

NOTE :

 Applicable if Communication Output.

:  Linear Cycle

Lean

:  Square root Cycle

SQrt

Change value by        key, or by        key.

Ctyp
Lean

CYCLE TYPE [LINEAR INPUT]

Value display for Analog input.

Values  :  

Default Value  :  

Lean

NOTE :

 Applicable for Analog Linear input only.

oFfS
0038

OFFSET FOR INPUT [FACTORY SET VALUE]

Offset Parameter for corresponding Input

Value  :  Factory Set for every Input

Default Value  :  

0038 

(As per Input)

NOTE :

 Factory set value, don’t change.

Ga1n
0007

GAIN FOR INPUT [FACTORY SET VALUE]

Gain Parameter for corresponding Input

Value  :  Factory Set for every Input

Default Value  :  

0007 

(As per Input)

NOTE :

 Factory set value, don’t change.

 

 

 

 

:  Selected

 YES

:  Not 

  no

DEAD

no

DEAD BAND

Operate Relay-1 on two setpoints

Values  :  

Default Value  :  

no

If set as YES, Only Relay-1 get operated in this 

parameter, relay get active on set point 1[SP1] 

value and deactivate in set point 2[SP2] value. 

Used for Level Control & Fan Operation.

Increase by        key, Decrease by        key.

WARNING

PERSONAL INJURY :

Configuration should be performed only by personnel who are technically competent to do 
so. Local Regulations regarding electrical & safety must be observed.

FAILURE TO COMPLY WITH THESE INSTRUCTIONS COULD RESULT IN DEATH OR SERIOUS INJURY.

 

d-sp
sp-1

DEFAULT SET POINT DISPLAY

Default selected Set Value [SV] to be displayed.

NOTE :

 Only one from SP-1 or SP-2 selected.

Increase by        key, Decrease by        key.

:  Set Point-1

 sp-1

:  Set Point-2

  sp-2

Values  :  

Default Value  :  

sp-1

Summary of Contents for UT-102

Page 1: ...6 www utplindia in www Model No UT 102 UNIVERSAL PROCESS INDICATOR CONTROLLER INSTRUCTION MANUAL M 96 x 96 Flame Proof UT 102 M COM www utplindia in RL 2 RL 1 RL 4 RL 3 102 0 102 0 UT 102 M COM www ut...

Page 2: ...ts Applying 240V AC to a controller rated for 12 24VDC will severely damage the controller and is a fire and smoke hazard This controller is suitable for connection to 230 15 VAC 50 Hz or 12 24 VDC po...

Page 3: ...GRAMMING 3 1 OPERATION INTERFACE 3 2 MODE ACCESS FLOW CHART 4 1 CONFIGURATION MODE 4 OPERATIONAL MODES 4 2 SETUP MODE 4 3 CALIBRATION MODE 4 4 CHANGE PASSWORD MODE 4 5 ERROR MESSAGE 5 COMMUNICATION MO...

Page 4: ...ange in the mode Two different configuration levels provide easy access to parameters A4 digit security code perverts una uthorized changes Parameters can also be hidden to user to prevent improper co...

Page 5: ...ale ANALOG V I SPECIAL ON DEMAND 0 1 of Full Scale Automatic Software based self compensation Cold Junction Comp OPEN or OVER indication on display Sensor Break Info AS per Input Range Table Range Lim...

Page 6: ...5 26 D NC NO C RELAY 4 RS 485 D NC NO C RELAY 3 NC RELAY 2 NO C NC NO C RELAY 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B B OUTPUT Analog Out TPS 24VDC v SUPPLY E P UT 102 15 16 17 18 N T C mA Noise Filter...

Page 7: ...a status of parameter Press to change set points in normal view UP KEY UP Key allows increasing the value of a digit selected or changing the status of parameter in programming mode Press to change se...

Page 8: ...OMPLY WITH THESE INSTRUCTION COULD BE RESULT IN SERIOUS INJURY OR DEATH PV SV 3 2 Mode Access Flow Chart 8888 8888 Normal Mode Mode Selection Configuration Setup Mode Mode Change Password Mode Calibra...

Page 9: ...nge the type Up by key Down by key Range Input Type is as follows TC 4 spCL pt 1 1 5v 0 20 4 20 2 5v 10v CU53 Default Value 0000 tsp1 L on ALARM 1 RELAY ACTION Alarm Relay activation direction Values...

Page 10: ...for Analog Linear input only oFfS 0038 OFFSET FOR INPUT FACTORY SET VALUE Offset Parameter for corresponding Input Value Factory Set for every Input Default Value 0038 As per Input NOTE Factory set va...

Page 11: ...se by key Range Values between 199 9 to 999 9 Default Value 000 2 Hys1 000 2 HYSTERESIS ALARM 1 Value Diff between On and Off of Relay 1 Scroll the digit by key Increase by key Range Values between 19...

Page 12: ...values range Range Default Value According to Input Type Note After Cali random value should be below 1000 appeared in display Range Default Value strt to start cal According to Output Type CALH strt...

Page 13: ...ontroller Controller circuit failed Check the power connection Check the supply voltage 4 4 Change Password Mode 4 5 Error Message Range Values Parameter PAsS 0000 CHANGE PASSWORD MODE PASSWORD Passwo...

Page 14: ...us protocol are as follows 5 4 MODBUS system schematic DATA READ ONLY SR NO 1 PROCESS VALUE PV PARAMETER ABSOLUTE ADDRESS ACCESS TYPE 40001 READ WRITE 3 SET POINT 1 SP1 40003 READ ONLY 2 DECIMAL POINT...

Page 15: ......

Reviews: