UNIVERSAL PROCESS INDICATOR & CONTROLLER

11

‘Change Password Mode’ Mode will shown by pressing        key, after 

CAL 

Mode display.

Open the Input Connection
Sensor Break or Sensor disconnected.

Sign 

Description 

Solution 

In case the following error messages appear in the display of controller, 
please refer to the Error message table below, or call technical support.

OPEN

Check the Input sensor wiring
Replace the sensor.
Check the Input sensor wiring
Check the Input type.
Adjust the Range

Excess of PV over the Span value

Check the Input sensor wiring
Check the Input type.
Adjust the Range

Shortage of PV over the Low value

vndr

Over

All LED’s and 

display not light

No power to the controller
Controller circuit failed

Check the power connection
Check the supply voltage.

4.4       Change Password Mode

4.5       Error Message.

 

Range / Values

Parameter

PAsS
0000

CHANGE PASSWORD MODE PASSWORD

Password for Change Password Mode.

Display

Scroll the digit by        key, Increase by        key.

Range  :  Values between 

0000

 to 

9999

Default Value  :  

0000

opas

0000

OLD EXISTING PASSWORD

Old - Default or Existing Password

Scroll the digit by        key, Increase by        key.

 

Range  :  Values between 

0000

 to 

9999

Default Value  :  

0000

npas

8888

NEW DESIRED PASSWORD

Set new Required Desired Password

Range  :  Values between 

0000

 to 

9999

Default Value  : As per new required.

(Any value)

Scroll the digit by        key, Increase by        key.

 

 

  

 

CAUTION 

PASSWORD PRECAUTIONS

FAILURE TO COMPLY WITH THESE INSTRUCTION MAY RESULT IN INSTRUMENT DAMAGE

*

*

              After Changing old password, all parameter are locked. All Modes are not 
              accessible without new password.

              Changed password should be remembered , it cannot be Reset at site.

Summary of Contents for UT-102

Page 1: ...6 www utplindia in www Model No UT 102 UNIVERSAL PROCESS INDICATOR CONTROLLER INSTRUCTION MANUAL M 96 x 96 Flame Proof UT 102 M COM www utplindia in RL 2 RL 1 RL 4 RL 3 102 0 102 0 UT 102 M COM www ut...

Page 2: ...ts Applying 240V AC to a controller rated for 12 24VDC will severely damage the controller and is a fire and smoke hazard This controller is suitable for connection to 230 15 VAC 50 Hz or 12 24 VDC po...

Page 3: ...GRAMMING 3 1 OPERATION INTERFACE 3 2 MODE ACCESS FLOW CHART 4 1 CONFIGURATION MODE 4 OPERATIONAL MODES 4 2 SETUP MODE 4 3 CALIBRATION MODE 4 4 CHANGE PASSWORD MODE 4 5 ERROR MESSAGE 5 COMMUNICATION MO...

Page 4: ...ange in the mode Two different configuration levels provide easy access to parameters A4 digit security code perverts una uthorized changes Parameters can also be hidden to user to prevent improper co...

Page 5: ...ale ANALOG V I SPECIAL ON DEMAND 0 1 of Full Scale Automatic Software based self compensation Cold Junction Comp OPEN or OVER indication on display Sensor Break Info AS per Input Range Table Range Lim...

Page 6: ...5 26 D NC NO C RELAY 4 RS 485 D NC NO C RELAY 3 NC RELAY 2 NO C NC NO C RELAY 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B B OUTPUT Analog Out TPS 24VDC v SUPPLY E P UT 102 15 16 17 18 N T C mA Noise Filter...

Page 7: ...a status of parameter Press to change set points in normal view UP KEY UP Key allows increasing the value of a digit selected or changing the status of parameter in programming mode Press to change se...

Page 8: ...OMPLY WITH THESE INSTRUCTION COULD BE RESULT IN SERIOUS INJURY OR DEATH PV SV 3 2 Mode Access Flow Chart 8888 8888 Normal Mode Mode Selection Configuration Setup Mode Mode Change Password Mode Calibra...

Page 9: ...nge the type Up by key Down by key Range Input Type is as follows TC 4 spCL pt 1 1 5v 0 20 4 20 2 5v 10v CU53 Default Value 0000 tsp1 L on ALARM 1 RELAY ACTION Alarm Relay activation direction Values...

Page 10: ...for Analog Linear input only oFfS 0038 OFFSET FOR INPUT FACTORY SET VALUE Offset Parameter for corresponding Input Value Factory Set for every Input Default Value 0038 As per Input NOTE Factory set va...

Page 11: ...se by key Range Values between 199 9 to 999 9 Default Value 000 2 Hys1 000 2 HYSTERESIS ALARM 1 Value Diff between On and Off of Relay 1 Scroll the digit by key Increase by key Range Values between 19...

Page 12: ...values range Range Default Value According to Input Type Note After Cali random value should be below 1000 appeared in display Range Default Value strt to start cal According to Output Type CALH strt...

Page 13: ...ontroller Controller circuit failed Check the power connection Check the supply voltage 4 4 Change Password Mode 4 5 Error Message Range Values Parameter PAsS 0000 CHANGE PASSWORD MODE PASSWORD Passwo...

Page 14: ...us protocol are as follows 5 4 MODBUS system schematic DATA READ ONLY SR NO 1 PROCESS VALUE PV PARAMETER ABSOLUTE ADDRESS ACCESS TYPE 40001 READ WRITE 3 SET POINT 1 SP1 40003 READ ONLY 2 DECIMAL POINT...

Page 15: ......

Reviews: