UT-102
UNIVERSAL PROCESS INDICATOR & CONTROLLER
10
‘Calibration Mode’ Mode will shown by pressing key, after
Setp
Mode display.
4.3 Calibration Mode
Range / Values
Parameter
pass
0000
CALIBRATION MODE PASSWORD
Password for Calibration Mode Parameters
Display
Scroll the digit by key, Increase by key.
Range : Values between
0000
to
9999
Default Value :
0000
CALz
----
CALIBRATION ZERO or LOW INPUT
Calibration Zero / Low at Low / Zero PV Input.
NOTE :
After Zero Cal. press key for next Para.
Apply Low signal [as per input] & press key.
Range :
Default Value :
----
According to Input Type
CALS
----
CALIBRATION SPAN or HIGH INPUT
Calibration Span / High at Span / High PV Input.
NOTE :
After Span Cal. press key for next para.
Apply High signal [as per input] & press key.
CALL
strt
CALIBRATION LOW [RETRANSMISSION] OUTPUT
Calibration desired Low Output at PV Display.
NOTE :
After out low cal. press key for next Para.
Set output by , & key, press key
for desired low measured output achieved.
Note :
After Calibration random value
appeared in display, as per input.
Refer below Table for Cal. values range.
Note :
After Calibration random value
appeared in display, as per input.
Refer below Table for Cal. values range.
Range :
Default Value :
----
According to Input Type
Note :
After Cali. random value should be
below
1000
appeared in display.
Range :
Default Value :
strt
-> to start cal.
According to Output Type
CALH
strt
CALIBRATION HIGH [RETRANSMISSION] OUTPUT
Calibration desired High Output at PV Display.
NOTE :
After out low cal. press key for next Para.
Set output by , & key, press key
for desired high measured output achieved.
Range :
Default Value :
strt
-> to start cal.
According to Output Type
Note :
After Cali. random value should be
below
8000
appeared in display.
CALa
0032
CALIBRATION AMBIENT [THERMO COUPLE INP.]
Ambient adjustment for compensation [T/C Inp.]
NOTE :
After Amb. Cal. press key for exit.
Set Ambient Temp by & key,press key.
Note :
After Calibration random value
appeared in display, as per input.
Range :
Default Value :
0032
As per Ambient Temperature.
0100
~
0600
0200
~
1000
0200
~
1000
0200
~
1000
0200
~
1000
0200
~
1000
7000
~
8000
7000
~
8000
7000
~
8000
7000
~
8000
7000
~
8000
7000
~
8000
INPUT
J - T/C
K - T/C
R - T/C
S - T/C
T - T/C
E - T/C
0 mV
0 mV
0 mV
ZERO VALUE
FEED VALUE
COUNT
SPAN VALUE
FEED VALUE
COUNT
0 mV
0 mV
0 mV
18 mV
18 mV
42 mV
42 mV
42 mV
18 mV
INPUT
ZERO VALUE
FEED VALUE
COUNT
SPAN VALUE
FEED VALUE
COUNT
0100
~
0600
0100
~
1000
0100
~
1000
0100
~
1000
0900
~
1500
7000
~
8000
7000
~
8000
7000
~
8000
7000
~
8000
2000
~
3000
4 ~ 20mA
0 ~ 20mA
1 ~ 5 VDC
10VDC
PT-100
4 mA
0 mA
1 VDC
0 VDC
20 mA
20 mA
5 VDC
10 VDC
CALIBRATION VALUES :
0°C
[100.0Ω]
100°C
[138.51Ω]