035-18525-001-B-0203
14
Unitary Products Group
FIGURE 12: BLOWER PERFORMANCE CURVE
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE
1, 2
NOTE: Refer to Form 550.13-AD1 for blower performance curves.
RPM range for the standard, factory-mounted drive components.
1Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the respective tables for the
resistance of these accessories and for additional motor and drive data.
2 Motors can be selected to operate into their service factor because they are located in the moving air stream, upstream of any heating device. Units with steam or
hot water coils are the only exception.
LA120
3000
3500
4000
4500
5000
5500
6000
6500
7000
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
External Static
CF
M
0 Turns
1 Turn
2 Turns
3 Turns
4 Turns
5 Turns
10 TON BLOWER PERFORMANCE
ESP
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
0.2
-
-
-
5775
680
2168
5402
650
1851
4990
616
1516
4571
582
1281
4250
548
1097
0.4
5521
713
2283
5409
684
1954
4810
653
1633
4326
618
1307
3785
582
1069
3484
550
903
0.6
4864
718
2006
4736
688
1695
4098
657
1353
3411
622
1052
2635
586
826
-
-
-
0.8
4221
722
1695
3780
693
1393
2860
661
1019
-
-
-
-
-
-
-
-
-
1
3223
728
1376
2625
697
1097
-
-
-
-
-
-
-
-
-
-
-
-
0 turns
1 turn
2 turns
3 turns
4 turns
5 turns
Exceeds Amperage rating of motor.