Unitary products group LA120 Installation Manual Download Page 12

035-18525-001-B-0203

12

Unitary Products Group

4. All pulleys are factory aligned.

5. All supply air motor pulleys are factory set at 2

“turns open”. 

After the supply air blower motor is operating,
adjust the resistances in both the supply and the
return duct system to balance the air distribution
throughout the conditioned space. The job specifi-
cations may require that this balancing be done by
someone other than the equipment installer.

To check the supply air CFM after the initial balancing
has been completed:

1. Drill two (2) 5/16-inch holes in the side panel as

shown in Figure  8.

2. Insert at least 8" of 1/4 inch tubing into each of

these holes for sufficient penetration into the air-
flow on both sides of the evaporator coil.

 

3. Using an inclined manometer, determine the pres-

sure drop across a dry evaporator coil.  Since the
moisture on an evaporator coil may vary greatly,
measuring the pressure drop across a wet coil
under field conditions would be inaccurate.  To
assure a dry coil, the refrigerant system should be
de-activated while the test is being run.

4. Knowing the pressure drop across a dry coil, the

actual CFM through the unit can be determined
from the curve in Figure  9.

If the CFM is above or below the specified valve, the
supply air motor pulley may have to be readjusted.
After on hour of operation, check the belt and pulleys
for tightness and alignment.

After readings have been obtained, remove the tubes
and seal up the drilled holes in the side panel.  5/16"
dot plugs (P/N 029-12880) are available through nor-
mal York parts ordering procedures.

FIGURE 9: TYPICAL MOTOR MOUNTING 

ASSEMBLY

B

A

(DO NOT LOOSEN)

MOTOR

MOTOR MOUNT

C

FIGURE 10: HOLE LOCATIONS FOR PRESSURE 

DROP READINGS

Failure to properly adjust the total system air
quantity can result in extensive blower dam-
age.

5 / 1 6 "

H O L E

5 / 1 6 "

H O L E

1 8 "

7 "

2 2 "

1 0 "

E V A P O R A T O R

C O I L

F I L T E R S

C O I L   S E C T I O N

Summary of Contents for LA120

Page 1: ...IONS 4 AGENCY APPROVALS 4 INSPECTION 4 INSTALLATION 6 MAINTENANCE 16 NOTES CAUTIONS AND WARNINGS Installer should pay particular attention to the words NOTE CAUTION and WARNING Notes are intended to c...

Page 2: ...ION 8 4 SUPPLY AIR PLENUM ACCESSORY 9 5 BASE ACCESSORY VERTICAL ONLY 9 6 RECOMMENDED DRAIN PIPING 10 7 RETURN AIR GRILLE ACCESSORY VERTICAL 10 Fig Pg 8 FIELD WIRING DIAGRAMS FOR POWER SUPPLY 12 9 FIEL...

Page 3: ...tandard Efficiency 2 Pipe B R 22 Standard Efficiency 4 Pipe 120 Nominal Cooling Capacity MBH 090 7 1 2 Ton 120 10 Ton 150 12 1 2 Ton 180 15 Ton 240 20 Ton C Heat Type C Cooling Only 00 Nominal Heating...

Page 4: ...on this equipment The forms referenced in this instruction may be ordered from Standard Register 2101 West Tecumseh Road Norman Oklahoma 73069 Toll Free TEL 877 318 7920 Toll Free FAX 877 379 7920 Thi...

Page 5: ...provided in the filter rack Qty Size in 6 20 X 20 X 1 Face Area Sq Ft 16 7 Operating Charge Refrigerant 22 Lbs Oz 5 8 Weight Lbs Shipping 439 Operating 399 Accessory Weights Lbs Electric Heaters 10 K...

Page 6: ...e suspended from above as shown in Figure 1 Refer to Form 035 16622 001 for more information on the installation of the suspension accessory and for the individual load on each hanger rod A field adde...

Page 7: ...illips machine bolts that hold the coil and blower sections together A bolt is located near each corner 3 Move the blower section to the proper location 4 Attach the blower section to the coil section...

Page 8: ...CCESS OPENING FOR POWER SUPPLY WIRING 1 2 WIRING HARNESS LOCATION This opening in the bottom of the heater control box is used for the wiring harness that connects the heater accessory to the basic un...

Page 9: ...n and a sealing material such as permagum should be packed around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility Support all refrigerant lines at mini...

Page 10: ...ith these codes Route the power wires into the unit through one of the 7 8 knockouts in the panel with the supply air opening and connect them to the terminals on blower motor contactor 10M Route the...

Page 11: ...t is made by moving the blower motor mount ing plate Refer to Figure 7 Turning the adjustment bolt B moves the motor mounting plate up or down Note Never loosen the tow nuts C Two hex nuts A have to b...

Page 12: ...orator coil may vary greatly measuring the pressure drop across a wet coil under field conditions would be inaccurate To assure a dry coil the refrigerant system should be de activated while the test...

Page 13: ...Motor Blower HP Blower RPM Adjustable Motor Pulley Fixed Blower Pulley Belt Pitch Dia Inches Bore Inches Pitch Dia Inches Bore Inches Designation Pitch Lg Inches LA120 2 549 716 3 1 4 1 7 8 9 5 1 A55...

Page 14: ...ing air stream upstream of any heating device Units with steam or hot water coils are the only exception LA120 3000 3500 4000 4500 5000 5500 6000 6500 7000 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 1 1...

Page 15: ...1 9 1 0 2 1 8 2 5 8 K N O C K O U T F O R 1 5 8 O D S U C T I O N C O N N 3 2 3 8 1 8 7 8 6 5 1 2 5 7 8 B L O W E R S E C T I O N 7 1 4 1 6 1 2 7 8 1 9 3 8 2 1 7 8 6 0 3 4 B L O W E R M O T O R A N D...

Page 16: ...LUBRICATION The bearings for the blower shaft and the blower motors are permanently lubricated and should not require additional lubricant BELTS Maintain belt tension to extend belt life Replace when...

Reviews: