MAINTENANCE
EVAPORATOR COIL
Do not allow dirt to accumulate on the evaporator coil
or other parts of the evaporator air circuit. Clean as
often as necessary to assure good system perfor-
mance. Use a brush, vacuum cleaner attachment or
other suitable means.
FILTERS
The filters must be replaced as often as necessary to
assure good air flow and filtering action.
Refer to Figure 10 for filter access panel location.
DRAIN PAN
The drain pan should be inspected regularly to assure
proper drainage.
LUBRICATION
The bearings for the blower shaft and the blower
motors are permanently lubricated and should not
require additional lubricant.
BELTS
Maintain belt tension to extend belt life. Replace when
signs of failure begin to appear.
MINIMUM CLEARANCES
Side Air with RETURN AIR opening
24”
Side with SUPPLY AIR opening
1
1.
Overall dimension of the unit will vary if an electric heater, a
supply air plenum or a base is used.
24”
Side with PIPING CONNECTIONS
2
2.
This dimension is required for removal of the DX coil. Only 26”
is required for normal servicing.
61”
Side opposite PIPING CONNECTIONS
3
3.
If the DX coil has to be removed, this dimension is required to
loosen screws that secure the coil to the unit frame. This dimen-
sion will also be required for blower motor access if the piping
connections are made on the opposite side of the unit.
26”
Bottom
4
4.
Allow enough clearance to trap the condensate drain lines.
-