035-19400-000-A-0403
Unitary Products Group
5
MODEL
BUP
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR OUTDOOR
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN.
MAX.
RLA
LRA
024
208/230-1-60
187
253
9.3
57.0
1.1
5.0
17.7
25
25
0.96
40
030
208/230-1-60
187
253
15.0
72.5
1.1
5.0
24.9
35
35
0.96
40
208/230-3-60
187
253
10.0
63.0
1.1
5.0
18.6
25
25
0.96
75
460-3-60
414
504
5.0
31.0
0.6
5.0
11.9
15
15
0.96
75
036
208/230-1-60
187
253
17.2
94.0
1.1
7.3
29.9
45
45
0.96
40
208/230-3-60
187
253
11.4
78.0
1.1
7.3
22.7
30
30
0.96
75
460-3-60
414
504
5.7
40.0
0.6
7.3
15.4
20
20
0.96
75
042
208/230-1-60
187
253
20.0
104.0
1.1
7.3
33.4
50
50
0.96
40
208/230-3-60
187
253
13.9
88.0
1.1
7.3
25.8
35
35
0.96
75
460-3-60
414
504
6.4
44.0
0.6
7.3
16.1
20
20
0.96
75
048
208/230-1-60
187
253
23.4
126.0
1.5
7.3
38.1
60
60
0.96
40
208/230-3-60
187
253
13.0
93.0
1.5
7.3
25.1
35
35
0.96
75
460-3-60
414
504
6.4
46.5
0.8
7.3
16.3
20
20
0.96
75
1 = Rated in accordance with ARI Standard 110, utilization range A.
2 = Dual element, time delay type.
TABLE 4 -
ELECTRICAL DATA (BASIC UNIT)
ELECTRIC HEAT
CORRECTION
FACTORS
NOMINAL VOLTAGE
VOLTAGE
KW CAP. MULTIPLIER
240
208
230
.75
.92
480
460
.92