background image

All units require certain clearances for proper operation and
service. Refer to Figures 3 & 4 for the clearances required for
construction, servicing and proper unit operation.

WARNING: Do not permit overhanging structures or shrubs to

obstruct the condenser air discharge outlet.

DUCT WORK

These units are adaptable to downflow use as well as rear sup-
ply and return air duct openings. To convert to downflow, use
the following steps:

1. Remove the duct covers found in the bottom return and

supply air duct openings. There are four (4) screws secur-
ing each duct cover (save these screws to use later).

2. Install the duct covers, removed in step one, to the rear

supply and return air duct openings. Secure with the four
(4) screws used in step one.

3. Seal duct covers with silicone caulk.

Downflow units must have an “L”-shaped supply duct without
any outlets or registers located below the outlet of the unit.

Duct work should be designed and sized according to the
methods of the Air Conditioning Contractors of America
(ACCA), as set forth in their Manual D.

A closed return duct system shall be used. This shall not pre-
clude use of economizers or ventilation air intake. Flexible
joints may be used in the supply and return duct work to mini-
mize the transmission of noise.

CAUTION: When fastening duct work to the side duct flanges on

the unit, insert the screws through the duct flanges only.
DO NOT insert the screws through the casing. Outdoor
duct work must be insulated and waterproofed.

NOTE: Be sure to note supply and return openings.

Refer to Figure 4 for information concerning rear and bottom
supply and return air duct openings.

FILTERS

Single phase units are shipped without a filter and it is the respon-
sibility of the installer to secure a filter

in the return air ductwork

or install a Filter/Frame Kit

(1FF0114).

A filter rack and high velocity filters are standard on three phase
units.

Filters must always be used and must be kept clean. When fil-
ters become dirt laden, insufficient air is delivered by the
blower, decreasing your unit's efficiency and increasing operat-
ing costs and wear-and-tear on the unit and controls.

Filters should be checked monthly especially since this unit is
used for both heating and cooling.

CONDENSATE DRAIN

A condensate trap is required to be installed in the condensate
drain. The plumbing must conform to local codes. Use a seal-
ing compound on male pipe threads. Install the condensate
drain line (

!

"

" NPTF) to spill into an open drain.

SERVICE ACCESS

Access to all serviceable components is provided by the follow-
ing removable panels:

Blower service access

Electrical/Filter access

Compressor service access

Refer to Figures 3 & 4 for location of these access panels and
minimum clearances.

THERMOSTAT

The room thermostat should be located on an inside wall ap-
proximately 56" above the floor where it will not be subject to
drafts, sun exposure or heat from electrical fixtures or appli-
ances. Follow manufacturer's instructions enclosed with the
thermostat for general installation procedure. Six color coded
insulated wires (minimum #18 AWG) should be used to con-
nect thermostat to unit. See Figure 2.

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the current
N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances.
The unit must be electrically grounded in accordance with local
codes or, in their absence, with the N.E.C./C.E.C. Voltage tol-
erances which must be maintained at the compressor termi-
nals during starting and running conditions are indicated on the
unit Rating Plate and Table 3.

The wiring entering the cabinet must be provided with me-
chanical strain relief.

A fused disconnect switch should be field provided for the unit. If
any of the wire supplied with the unit must be replaced, replace-
ment wire must be of the type shown on the wiring diagram.

Electrical line must be sized properly to carry the load. Each
unit must be wired with a separate branch circuit fed directly
from the meter panel and properly fused.

Refer to Figure 2 for typical field wiring and to the appropriate unit
wiring diagram for control circuit and power wiring information.

COMPRESSORS

Units are shipped with compressor mountings factory-adjusted
and ready for operation.

CAUTION: Do Not loosen compressor mounting bolts.

035-19400-000-A-0403

Unitary Products Group

3

Summary of Contents for BAUP024

Page 1: ...Pre start Post start Check List 035 16605 001 Electric Heater Accessory REPLACEMENT PARTS Refer to User s Maintenance and Service Information Manual for complete listing of replacement parts on this...

Page 2: ...unit is near the place of installation Rig unit with slings placed under the unit Spreader bars of suffi cient length should be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS...

Page 3: ...at ing costs and wear and tear on the unit and controls Filters should be checked monthly especially since this unit is used for both heating and cooling CONDENSATE DRAIN A condensate trap is required...

Page 4: ...COMPRESSOR HERMETIC Type Qty 1 Reciprocating Scroll Scroll Scroll Scroll FIG 2 TYPICAL FIELD WIRING DIAGRAM POWER WIRING REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCON NECT SWITCH WIRING OVERCURRE...

Page 5: ...53 17 2 94 0 1 1 7 3 29 9 45 45 0 96 40 208 230 3 60 187 253 11 4 78 0 1 1 7 3 22 7 30 30 0 96 75 460 3 60 414 504 5 7 40 0 0 6 7 3 15 4 20 20 0 96 75 042 208 230 1 60 187 253 20 0 104 0 1 1 7 3 33 4...

Page 6: ...NH04501025 2NH04501525 7 5 10 0 11 3 15 0 20 8 24 1 31 3 36 1 44 7 48 7 57 7 63 7 45 50 60 70 45 50 60 70 036 208 230 3 60 11 4 78 0 1 1 7 3 2NH04501025 2NH04501525 7 5 10 0 11 3 15 0 20 8 24 1 31 3 3...

Page 7: ...01 0 11 0 11 0 12 NOTE 1 Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table 2 The pressure thru the economizer is greater for...

Page 8: ...L OVERALL 4 1 2 All dimensions are in inches They are subject to change without notice Certified dimensions will be provided upon request UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED 49 OVERALL SIDE...

Page 9: ...outdoor coil temperatures indicate that defrosting is necessary When coil temperature is below the ini tiate point for the ambient temperature continuously for 4 1 2 minutes the heat pump is put into...

Page 10: ...OFF HEATER BANK 3 ELEC HEAT INSTANT OFF HEATER BANK 2 ELEC HEAT SEC DELAY OFF HEATER BANK 1 ELEC HEAT 1 SEC DELAY OFF FAN 10 SEC DELAY OFF G Y W ON FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON...

Page 11: ...OFF G W ON FAN INSTANT ON HEATER BANK 1 2 3 ELEC HEAT INSTANT ON HEATER BANK 4 5 6 ELEC HEAT 10 SEC DELAY ON OFF HEATER BANK 4 5 6 ELEC HEAT INSTANT OFF HEATER BANK 1 2 3 ELEC HEAT SEC DELAY OFF FAN 1...

Page 12: ...door coil surface or other parts in the air circuit Cleaning should be as often as necessary to keep the coil clean Use a brush vacuum cleaner attachment or other suitable means If water is used to cl...

Page 13: ...Unitary Products Group 13 035 19400 000 A 0403 FIG 5 TYPICAL WIRING DIAGRAM BUP MODELS 208 230 1 60 POWER SUPPLY...

Page 14: ...14 Unitary Products Group 035 19400 000 A 0403 FIG 6 TYPICAL WIRING DIAGRAM BUP 208 230 3 60 POWER SUPPLY...

Page 15: ...Unitary Products Group 15 035 19400 000 A 0403 FIG 7 TYPICAL WIRING DIAGRAM BUP 460 3 60 POWER SUPPLY...

Page 16: ...oducts Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2003 All Rights Reserved Supersedes Nothing 035 19400 0...

Reviews: