035-19400-000-A-0403

6

Unitary Products Group

TABLE 5 -

ELECTRICAL DATA (13 SEER HEAT PUMP / ELECTRIC HEAT)

MODEL

BUP

POWER

SUPPLY

COMPRESSOR

COND.

FAN

MOTOR

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

ELECTRIC HEAT ACCESSORY

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,



AMPS

MAX.

HACR

‚

BREAKER

SIZE

RLA

LRA

MODEL NO.

KW

TOTAL

AMPS

024 208/230-1-60

9.3

57.0

1.1

5.0

2NH04500506
2NH04500706
2NH04501006

3.8 / 5.0 *
5.6 / 7.5 *

7.5 / 10.0 *

18.1 / 20.8
27.1 / 31.3
36.1 / 41.7

40.3 / 43.8
51.6 / 56.8
62.9 / 69.8

45 / 45
60 / 60
70 / 70

45 / 45
60 / 60
70 / 70

030 208/230-1-60

15.0

72.5

1.1

5.0

2NH04500506
2NH04500706
2NH04501006
2NH04501506

3.8 / 5.0 *
5.6 / 7.5 *

7.5 / 10.0 *

11.3 / 15.0 *

18.1 / 20.8
27.3 / 31.3
36.1 / 41.7
54.2 / 62.5

47.4 / 50.9
58.7 / 63.9
70.0 / 76.9

92.6 / 103.0

50 / 60
60 / 70
70 / 80

100 / 110

50 / 60
60 / 70
70 / 80

100 / 110

036 208/230-1-60

17.2

94.0

1.1

7.3

2NH04500506
2NH04500706
2NH04501006
2NH04501506

3.8 / 5.0 *
5.6 / 7.5 *

7.5 / 10.0 *

11.3 / 15.0 *

18.1 / 20.8
27.1 / 31.3
36.1 / 41.7
54.2 / 62.5

52.5 / 55.9
63.8 / 69.0
75.0 / 82.0

97.6 / 108.0

60 / 60
70 / 70
80 / 90

100 / 110

60 / 60
70 / 70
80 / 90

100 / 110

042 208/230-1-60

20.0

104.0

1.1

7.3

2NP04501006
2NP04501506

7.5 / 10.0 *

11.3 / 15.0 *

36.1 / 41.7
54.2 / 62.5

78.5 / 85.5

101.1 / 111.5

80 / 90

100 / 125

80 / 90

100 / 125

048 208/230-1-60

23.4

126.0

1.5

7.3

2NP04501006
2NP04501506
2NP04502006
2NP04502506

7.5 / 10.0 *

11.3 / 15.0 *

15.0 / 20.0 *
18.8 / 25.0 *

36.1 / 41.7
54.2 / 62.5
72.2 / 83.3

90.3 / 104.2

83.2 / 90.1

105.8 / 116.2

128.3 / 142.2
150.9 / 168.3

90 / 90

110 / 125

150 / 150
175 / 175

90 / 90

110 / 125

150 / 150
175 / 175

030 208/230-3-60

10.0

63.0

1.1

5.0

2NH04501025
2NH04501525

7.5 / 10.0 *

11.3 / 15.0 *

20.8 / 24.1
31.3 / 36.1

44.7 / 48.7
57.7 / 63.7

45 / 50
60 / 70

45 / 50
60 / 70

036 208/230-3-60

11.4

78.0

1.1

7.3

2NH04501025
2NH04501525

7.5 / 10.0 *

11.3 / 15.0 *

20.8 / 24.1
31.3 / 36.1

48.7 / 52.7
61.7 / 67.8

60 / 60
70 / 80

60 / 60
70 / 80

042 208/230-3-60

13.9

88.0

1.1

7.3

2NP04501025
2NP04501525

7.5 / 10.0 *

11.3 / 15.0 *

20.8 / 24.1
31.3 / 36.1

51.8 / 55.8
64.9 / 70.9

50 / 60
70 / 70

50 / 60
70 / 70

048 208/230-3-60

13.0

93.0

1.5

7.3

2NP04501025
2NP04501525
2NP04502025
2NP04502525

7.5 / 10.0 *

11.3 / 15.0 *

15.0 / 20.0 *
18.8 / 25.0 *

20.8 / 24.1
31.3 / 36.1
41.7 / 48.1
52.1 / 60.1

51.1 / 55.1
64.1 / 70.2
77.2 / 85.2

90.2 / 100.2

60 / 60
70 / 80
80 / 90

100 / 100

60 / 60
70 / 80
80 / 90

100 / 100

030

460-3-60

5.0

31.0

0.6

5.0

2NH04501046
2NH04501546

10.0**
15.0**

12.0
18.0

27.5
35.4

30
40

30
40

036

460-3-60

5.7

40.0

0.6

7.3

2NH04501046
2NH04501546

10.0**
15.0**

12.0
18.0

30.7
38.6

35
40

35
40

042

460-3-60

6.4

44.0

0.6

7.3

2NP04501046
2NP04501546

10.0**
15.0**

12.0
18.0

31.6
29.4

35
40

35
40

048

460-3-60

6.4

46.5

0.8

7.3

2NP04501046
2NP04501546
2NH04502046
2NH04502546

10.0**
15.0**
20.0**
25.0**

12.0
18.0
24.1
30.1

31.8
39.6
47.5
55.3

35
40
50
60

35
40
50
60

Q

= Dual element, time delay type.

R

= Standard circuit breakers may be used in Canada and on applications

over 60 amps where the heaters are separately fused.

*

= KW listed is for 240 volts, use table on previous page for 208 or 230 volts.

**

= KW listed is for 480 volts, use table on previous page for 460 volts.

Q

All units are factory set to TB2-A.

Above data includes allowances for a dry indoor coil and no filters. For additional pressure drops, refer to the “Additional Static Pressure Resistance” table.

 

 

 

    

       

 

     

 

 

 

       

 

 

 

 

     

 

 

 

!

 

     

 

 

 !

 

 

       

 

 

 

 

 

 

 

!!

   

  

  

 

!

   

 

  

  

 

!

 

 

 

 !!

!

!

 

   

 

! !

       

 

 

!!

TABLE 6 -

SIDE AND BOTTOM SUPPLY AIR BLOWER PERFORMANCE (208/230/460 VOLT



)

Summary of Contents for BAUP024

Page 1: ...Pre start Post start Check List 035 16605 001 Electric Heater Accessory REPLACEMENT PARTS Refer to User s Maintenance and Service Information Manual for complete listing of replacement parts on this...

Page 2: ...unit is near the place of installation Rig unit with slings placed under the unit Spreader bars of suffi cient length should be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS...

Page 3: ...at ing costs and wear and tear on the unit and controls Filters should be checked monthly especially since this unit is used for both heating and cooling CONDENSATE DRAIN A condensate trap is required...

Page 4: ...COMPRESSOR HERMETIC Type Qty 1 Reciprocating Scroll Scroll Scroll Scroll FIG 2 TYPICAL FIELD WIRING DIAGRAM POWER WIRING REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCON NECT SWITCH WIRING OVERCURRE...

Page 5: ...53 17 2 94 0 1 1 7 3 29 9 45 45 0 96 40 208 230 3 60 187 253 11 4 78 0 1 1 7 3 22 7 30 30 0 96 75 460 3 60 414 504 5 7 40 0 0 6 7 3 15 4 20 20 0 96 75 042 208 230 1 60 187 253 20 0 104 0 1 1 7 3 33 4...

Page 6: ...NH04501025 2NH04501525 7 5 10 0 11 3 15 0 20 8 24 1 31 3 36 1 44 7 48 7 57 7 63 7 45 50 60 70 45 50 60 70 036 208 230 3 60 11 4 78 0 1 1 7 3 2NH04501025 2NH04501525 7 5 10 0 11 3 15 0 20 8 24 1 31 3 3...

Page 7: ...01 0 11 0 11 0 12 NOTE 1 Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table 2 The pressure thru the economizer is greater for...

Page 8: ...L OVERALL 4 1 2 All dimensions are in inches They are subject to change without notice Certified dimensions will be provided upon request UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED 49 OVERALL SIDE...

Page 9: ...outdoor coil temperatures indicate that defrosting is necessary When coil temperature is below the ini tiate point for the ambient temperature continuously for 4 1 2 minutes the heat pump is put into...

Page 10: ...OFF HEATER BANK 3 ELEC HEAT INSTANT OFF HEATER BANK 2 ELEC HEAT SEC DELAY OFF HEATER BANK 1 ELEC HEAT 1 SEC DELAY OFF FAN 10 SEC DELAY OFF G Y W ON FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON...

Page 11: ...OFF G W ON FAN INSTANT ON HEATER BANK 1 2 3 ELEC HEAT INSTANT ON HEATER BANK 4 5 6 ELEC HEAT 10 SEC DELAY ON OFF HEATER BANK 4 5 6 ELEC HEAT INSTANT OFF HEATER BANK 1 2 3 ELEC HEAT SEC DELAY OFF FAN 1...

Page 12: ...door coil surface or other parts in the air circuit Cleaning should be as often as necessary to keep the coil clean Use a brush vacuum cleaner attachment or other suitable means If water is used to cl...

Page 13: ...Unitary Products Group 13 035 19400 000 A 0403 FIG 5 TYPICAL WIRING DIAGRAM BUP MODELS 208 230 1 60 POWER SUPPLY...