Unitary products group AHC9V UP Installation Manual Download Page 17

271043-UIM-B-0707

Unitary Products Group

17

Combustion Air Source From Outdoors

The blocking effects of louvers, grilles and screens must be given con-
sideration in calculating free area. If the free area of a specific louver or
grille is not known, refer to Table 12, to estimate free area.

*

Do not use less than 1/4” (0.635 cm) mesh.

+

Free area or louvers and grille varies widely; the installer should follow lou-
ver or grille 
manufacturer’s instructions.

Dampers, Louvers and Grilles (Canada Only)

1.

The free area of a supply air opening shall be calculated by sub-
tracting the blockage area of all fixed louvers grilles or screens
from the gross area of the opening.

2.

Apertures in a fixed louver, a grille, or screen shall have no dimen-
sion smaller than 0.25” (6.4 mm).

3.

A manually operated damper or manually adjustable louvers are
not permitted for use.

4.

A automatically operated damper or automatically adjustable lou-
vers shall be interlocked so that the main burner cannot operate
unless either the damper or the louver is in the fully open position

This type of installation requires that the supply air to the appli-
ance(s) be of a sufficient amount to support all of the appliance(s)
in the area. Operation of a mechanical exhaust, such as an exhaust
fan, kitchen ventilation system, clothes dryer or fireplace may cre-
ate conditions requiring special attention to avoid unsatisfactory
operation of gas appliances. A venting problem or a lack of supply
air will result in a hazardous condition, which can cause the appli-
ance to soot and generate dangerous levels of CARBON MONOX-
IDE, which can lead to serious injury, property damage and / or
death.

TABLE 12: 

Estimated Free Area

Wood or Metal

Louvers or Grilles

Wood 20-25%*

Metal 60-70% *

1/4” (0.635 cm)

mesh or larger 100%

TABLE 13: 

Free Area

BTUH Input 

Rating

Minimum Free Area Required for Each Opening

Horizontal Duct 

(2,000 BTUH)

Vertical Duct or 

Opening to Outside 

(4,000 BTUH)

Round Duct

(4,000 BTUH)

40,000

20 sq. in. (129 cm

2

)

10 sq. in. (64 cm

2

)

4” (10 cm)

60,000

30 sq. in. (194 cm

2

)

15 sq. in. (97 cm

2

)

5” (13 cm)

80,000

40 sq. in. (258 cm

2

) 20 sq. in. (129 cm

2

)

5” (13 cm)

100,000

50 sq. in. (523 cm

2

) 25 sq. in. (161 cm

2

)

6” (15 cm)

120,000

60 sq. in. (387 cm

2

) 30 sq. in. (194 cm

2

)

7” (18 cm)

EXAMPLE: Determining Free Area.
Appliance 1Appliance 

2Total 

Input

100,000 

+ 30,000 = (130,000 

÷

 4,000) = 32.5 Sq. In. Vertical

Appliance 1Appliance 

2Total 

Input

100,000 

+ 30,000 = (130,000 

÷

 2,000) = 65 Sq. In. Horizontal

TABLE 14: 

Unconfined Space Minimum Area in Square Inch

BTUH Input Rating

Minimum Free Area Required for Each Opening

40,000

40 (258 cm

2

)

60,000

60 (387 cm

2

)

80,000

80 (516 cm

2

)

100,000

100 (645 cm

2

)

120,000

120 (774 cm

2

)

 FIGURE 17:  

Outside and Ambient Combustion Air

GABLE
VENT

GAS
VENT

SOFFIT
VENT

VENTILATED

ATTIC

TOP ABOVE
INSULATION

OPTIONAL
INLET (a)

OUTLET
AIR (a)

VENTILATED

CRAWL SPACE

GAS
WATER
HEATER

VENTILATED

ATTIC

TOP ABOVE
INSULATION

GAS
VENT

GABLE
VENT

SOFFIT
VENT

GAS
WATER
HEATER

INLET
AIR (a)

INLET
AIR (b)

GAS
VENT

OUTLET
AIR (a)

OUTLET
AIR (b)

INLET
AIR (a)

INLET
AIR (b)

GAS
WATER
HEATER

FURNACE

1. An opening may be used in lieu of a duct to provide to provide the outside air

supply to an appliance unless otherwise permitted by the authority having
jurisdiction. The opening shall be located within 12” (30.5 cm) horizontally from,
the burner level of the appliance. Refer to “AIR SOURCE FROM OUTDOORS
AND VENT AND SUPPLY AIR SAFETY CHECK” in these instructions for
additional information and safety check procedure.

2. The duct shall be either metal, or a material meeting the class 1

requirements of CAN4-S110 Standard for Air Ducts.

3. The duct shall be least the same cross-sectional area as the free

area of the air supply inlet opening to which it connects.

4. The duct shall terminate within 12 in (30.5 cm) above, and

within 24 in (61 cm) horizontally from, the burner level of
the appliance having the largest input.

5. A square or rectangular shaped duct shall only be used

when the required free area of the supply opening is
9 in (58.06 cm ) or larger. When a square or rectangular
duct is used, its small dimension shall not be less than
3 in (7.6 cm).

2

2

6. An air inlet supply from outdoors shall be equipped with

a means to prevent the direct entry of rain and wind.
Such means shall not reduce the required free area of
the air supply opening.

7.

An air supply inlet opening from the outdoors shall
be located not less than 12” (30.5 cm) above the
outside grade level.

FURNACE

FURNACE

AIR SUPPLY OPENINGS AND DUCTS

COMBUSTION AIR SOURCE FROM OUTDOORS

1. Two permanent openings, one within 12 in (30.5 mm) of the top and

one within 12 in (30.5 mm) of bottom of the confined space,

shall communicate directly or by means of ducts

with the outdoors, crawl spaces or attic spaces.

Two

permanent openings,

2. One permanent openings, commencing within 12 in (30.5 mm)of the

top of the enclosure shall be permitted where the equipment has
clearances of at least 1 in (2.54 cm) from the sides and back and
6 in (15.24 cm) from the front of the appliance. The opening shall
communicate directly with the outdoors and shall have a minimum
free area of:

3. The duct shall be least the same cross-sectional area as the free

area of the air supply inlet opening to which it connects.

1 square in per 3000 Btu per hour (6.45

0.879 kW) of the

total input rating of all equipment located in the enclosure.

cm per

3

a.

Not less than the sum of all vent connectors in the confined space.

b.

4. The blocking effects of louvers, grilles and screens must be given

consideration in calculating free area. If the free area of a specific
louver aor grille is not known.

Summary of Contents for AHC9V UP

Page 1: ...electrical and mechanical codes LIST OF SECTIONS SAFETY 1 DUCTWORK 4 FILTERS 6 GAS PIPING 7 ELECTRICAL POWER 8 COMBUSTION AIR AND VENT SYSTEM 12 CONDENSATE PIPING 18 SAFETY CONTROLS 19 START UP AND AD...

Page 2: ...ible materials as listed under Clearances to Combustibles in Table 1 Provide clearances for servicing ensuring that service access is allowed for both the burners and blower These models ARE NOT CSA l...

Page 3: ...or and the furnace must be located or protected to avoid physical damage by vehicles The furnace area must not be used as a broom closet or for any other storage purposes as a fire hazard may be creat...

Page 4: ...NOTE When attaching duct flange do not shoot the screw down into the casing Use the formed flange intended for duct flange attachment The duct system is a very important part of the installation If th...

Page 5: ...e presence of leaks in the heat exchanger This access cover shall be attached in such a manner as to prevent leaks TABLE 2 Minimum Duct Sizing For Proper Airflow Input Cabinet Airflow Return1 Rectangu...

Page 6: ...provided with that accessory for proper hole cut size SECTION III FILTERS FILTER INSTALLATION All applications require the use of a filter Filters must be installed external to the furnace cabinet DO...

Page 7: ...igure 1 dimensions The inlet to the gas valve lines up directly with the opening in the left side of the furnace casing To line up with the opening in the right side of the casing two street ells shou...

Page 8: ...5 1 4 1 3 39 1 0 37 0 34 0 31 1100 1 3 1 2 1 1 41 0 0 34 0 31 0 28 2500 LP 4 1 3 8 3 5 93 2 LP 1 03 0 95 0 87 PROPANE AND HIGH ALTITUDE CONVERSION KITS It is very important to choose the correct kit...

Page 9: ...o the terminal board on the ignition module as shown in Figures 5 and 6 Electronic thermostats may require the common wire to be connected as shown in Figures 5 and 6 Apply strain relief to thermostat...

Page 10: ...ight O Reversing Valve Energized in Cool TWO STAGE AIR CONDITIONING Comfort Alert Interface HUM Dehumidification Open on Humidity Rise C 24 Volt Common C 24 Volt Common R 24 Volt Hot W2 Second Stage H...

Page 11: ...W2 Delay on furnace to OFF HM Humidistat BSG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary Heat W Auxiliary Heat Y...

Page 12: ...length listed in Table 8 is for the vent pip ing and the air intake piping separately For example if the table allows 65 equivalent feet for a particular model then the vent can have 65 equivalent fe...

Page 13: ...piping apply cement primer and the cement per the manufactures instructions Primer and cement must conform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent air...

Page 14: ...ns 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW C Clearance to permanently closed window 12 inches 30 cm 12 inches 30 cm D Vertical clearance to ventilated...

Page 15: ...systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone Refer to Figures 11 or 12 VENTING MULTIPLE UNITS Multiple units can be installed in a space or...

Page 16: ...vent Care should be taken to locate side vented systems where trees or shrubs will not block or restrict supply air from entering the terminal Also the terminal assembly should be located as far as p...

Page 17: ...LE VENT GAS VENT SOFFIT VENT VENTILATED ATTIC TOP ABOVE INSULATION OPTIONAL INLET a OUTLET AIR a VENTILATED CRAWL SPACE GAS WATER HEATER VENTILATED ATTIC TOP ABOVE INSULATION GAS VENT GABLE VENT SOFFI...

Page 18: ...Air The ventilated attic space or a crawl space from which the combustion air is taken must comply with the requirements specified in AIR SOURCE FROM OUTDOORS in this instruction or in Section 5 3 Air...

Page 19: ...e controls are mounted on the burner box assembly If the temper ature in the burner box exceeds its set point the ignition control and the gas valve are de energized The operation of this control indi...

Page 20: ...ll start and come up to speed Shortly after inducer start up the hot surface igniter will glow for about 17 seconds b After this warm up the ignition module will energize open the main gas valve c Aft...

Page 21: ...3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the...

Page 22: ...shown in Figure 21 The procedure below is used to adjust either the high fire manifold pressure or the low fire manifold pressure IMPORTANT The cap for the pressure regulator must be removed entirely...

Page 23: ...blown into the heated space The fan off timing may be adjusted by positioning the jumper on two of the four pins as shown in Figure 23 WITH BURNER BOX COVER IN PLACE WITH BURNER BOX COVER REMOVED FIG...

Page 24: ...een the R and W terminals The indoor fan motor is energized through the W1 heat terminal and runs on the speed selected on the HEAT tap of the control board Humidistat When a humidistat is installed i...

Page 25: ...T CODE STORAGE AND RETRIEVAL The control in this furnace is equipped with memory that will store up to five error codes to allow a service technician to diagnose problems more easily This memory will...

Page 26: ...A C 52 1 35 4 53 2 35 4 1560 1010 1620 1030 C B 44 2 28 6 45 9 29 2 1470 940 1500 960 B C 41 6 26 6 42 5 27 2 1370 890 1410 880 D B 38 8 25 2 39 9 24 9 1460 930 1490 920 C A 41 3 26 3 42 2 26 1 1250 7...

Page 27: ...in in2 cm2 In W C kPA In W C kPA In W C kPA 0 750 0 21 4 230 1484 0 01 0 00249 0 01 0 00249 0 15 0 03736 751 1000 21 25 28 32 330 2129 0 05 0 01245 0 05 0 01245 0 20 0 04982 1001 1250 28 33 35 40 330...

Page 28: ...Printed in U S A 271043 UIM B 0707 Copyright by York International Corp 2007 All rights reserved Supersedes 271043 UIM A 0407 Unitary 5005 Norman Products York OK Group Drive 73069 SECTION X WIRING D...

Reviews: