degrees Fahrenheit, press and hold the
MIN/MAX
button for 3 seconds in normal mode.
3.5
Backlight
Operation
To temporarily turn on the back light for five seconds, press the
any
button on the indoor sensor.
4
Adjustment
or
Calibration
Note:
The measured humidity range is between 10 and 99%. Humidity cannot be accurately
measured outside of this range. Thus, the humidity cannot be calibrated below 10% or above 99%.
The purpose of calibration is to fine tune or correct for any sensor error associated with the devices
margin of error. The measurement can be adjusted from the console to calibrate to a known source.
Calibration is only useful if you have a known calibrated source you can compare it against, and is
optional. This section discusses practices, procedures and sources for sensor calibration to reduce
manufacturing and degradation errors. Do not compare your readings obtained from sources such as
the internet, radio, television or newspapers. They are in a different location and typically update once
per hour.
The purpose of your weather station is to measure conditions of your surroundings, which vary
significantly from location to location.
4.1
Humidity
Calibration
To enter the humidity calibration mode, press and hold the
SET and MIN/MAX
buttons at the same
time for 3 seconds and the humidity value will begin flashing. Press the
CH/+
button to increase the
humidity and the
MIN/MAX/-
button to decrease the humidity reading in 1% increments. To rapidly
increase (or decrease) the humidity reading, press and hold the
CH/+
or
MIN/MAX/-
button.
To return the humidity to the actual or uncalibrated measurement, press the
SET
button.
will be displayed when the humidity calibrated measurement.
Once the displayed humidity equals the calibrated source, press and hold the
SET
button for three
seconds, or wait 15 seconds for timeout, and the humidity value will stop flashing.
4.2
Temperature
Calibration
To enter the temperature calibration mode, press and hold the
SET and CH/+
buttons for 3 seconds
and the temperature value will begin flashing. Press the
CH/+
button to increase the temperature and
the
MIN/MAX/-
button to decrease the temperature reading in 0.1° increments. To rapidly increase
(or decrease) the temperature reading, press and hold the
CH/+
or
MIN/MAX/-
button.
To return the temperature to the actual or uncalibrated measurement, press the
SET
button.
will be displayed when the humidity calibrated measurement.
Once the displayed temperature equals the calibrated source, press and hold the
SET
button for three
seconds, or wait 15 seconds for timeout, and the temperature value will stop flashing.
Discussion
:
Temperature errors can occur when a sensor is placed too close to a heat source (such
as a building structure, the ground or trees).