General Warning
Sageon II Bulk Product Manual
PM990-5201-00, Issue 6
1-1
1.
GENERAL WARNING
1.
This equipment has been designed to be used only in restricted access areas.
2.
This equipment must only be serviced by authorized and qualified service personnel.
3.
Operators should not attempt to repair faulty units. There are no operator serviceable parts inside. All fuses are only
replaced as part of a repair procedure in a repair facility by authorized personnel and not as a maintenance procedure on
site.
4.
The power Module magazine should be mounted in a rack that satisfies the requirements for electrical enclosures and fire
enclosures according to IEC60950 or equivalent standard. For open rack use, the back of the magazine must be fully
enclosed by its covers and the AC wiring terminations must be protected by either a grounded casing or an enclosure that
provides double insulation.
5.
The power shelves must be used with sufficient ventilation. After mounting, the air flow paths into and out of the
rectifiers must be unrestricted. Allow adequate flow for exhaust air out of the rack.
6.
Rectifiers are live at all times when the rectifier is plugged into the backplane connector. The input AC disconnection
device is the rectifier backplane connector.
7.
When removing modules, especially if the ambient temperature is high and the unit has been operating at maximum load,
avoid skin contact with the metal casing, as it may be too hot to touch. Pull the unit halfway out of the magazine and let
cool for 2-3 minutes before handling.