Installation
Sageon II Bulk Product Manual
PM990-5201-00, Issue 6
3-2
The AC input connections are located on the left side of the module. There are three (3) 400A & five (5) 600A 1” conduit
knockouts located along the left side, looking from the back, for the electrician. The AC feed should be wired as individually
protected feeds for each rectifier (recommended and preferred) to provide discrimination of fault protection devices. Where
the AC breaker option is integrated into the Power Module, each rectifier feed is individually protected and the installer is
only required to connect a single AC supply (1 phase) to the AC DIN rail terminations.
3.3
MAINS CONNECTIONS
Figure 3-2 AC Feed Terminations
3.3.1
Factory Supplied Configurations
Power shelves internal AC distribution, are configured with each rectifier hot line (L1) and neutral (L2), being terminated in
an individual DIN rail terminal block (beige). The grounding wire connects to the green/yellow terminal block (GND).
3.3.2
Single phase – individual protected external feeds
Connect each of the circuit breaker protected hot wires (L1) to the individual terminal blocks that feed each rectifier.
Connect the neutral wires to the respective neutral terminals (L2).