Page 33 of 39
Rev. 13
2: Temperature compensation
3: AC current display
4: AC voltage display
5: LCD sleep mode
6: Language
7: Battery current display
8 Formation
9: Battery test
10: x
11: x
12: x
13: x
14: x
15: x
Please do not modify this register without consulting the factory.
Note 8
Charger state – address: (15L hex)
7
6 5 4 3
2
1
0
0: Current limit
1: Equalize
2: Float
3: Battery test
4: Formation voltage
5: Formation current
6: Continuity Test Mode
7: Continuity Test passed. (if '1', Continuity Test failed)
This register is to indicate the charger operation mode: The charger can operate in 5 different modes: Current limited,
float, equalize, battery test and formation.
Note 9
Equalize mode start: address: (17 hex)
15 14 13 12 11 10
9
8
7
6
5
4
3 2 1
0
The equalize mode will kick in if one of the conditions is authorized
0: Eq
1: Manual
2: Periodical
3: Low DC volts
4: AC fail
5: Refresh
6: Remote (via contact)
7: Current limit
8: Charger start
9: x
10: x
11: x
12: x
13: x
14: x
15: x
This register is used for the charger equalize mode configuration.