Page 25 of 39
Rev. 13
Object 40 variation 0 (Analog output all variation)
Default: Object 40 variation 02 (16-Bit analog output with status)
Request
(slave must parse)
Response
(master must parse)
Codes function
Codes Qual (hex)
Codes function
Codes Qual (hex)
1 read
00,01,06
129-read
00,01
Point Signification Unit
Note
0 Unused
1 Float
voltage
Volt
note(1)
2 Equalize
voltage
Volt
note(1)
3
Float Current limit
Ampere
note(1)
4
Equalize Current limit
Ampere
note(1)
5 Unused
6
Nominal output voltage
Volt
note(1)
7
Nominal output current (Shunt1)
Ampere
note(1)
8 Formation
voltage
Volt
note(1)
9
Formation current
Ampere
note(1)
10 Formation
time
Hours
note(22)
11 Formation
relay
note(22)
12 Unused
13
Manual equalize time out
Hours
note(22)
14
Periodical equalize time out
Hours
note(22)
15
Periodical equalize period (delay)
Days
note(22)
16
DC Low volts equalize time out
Hours
note(22)
17
DC Low volts equalize
Volt
note(1)
18
AC fail equalize time out
Hours
note(22)
19
AC fail equalize delay
Seconds
note(22)
20
Refresh equalize time out
Minutes
note(22)
21
Refresh equalize period (delay)
Hours
note(22)
22
Remote equalize time out
Hours
note(22)
23
Current limit equalize time out
Hours
note(22)
24
Current limit equalize delay
Seconds
note(22)
25
Post Charge Voltage delay
Minutes
note(22)
26
Post Charge current delay
Minutes
note(22)
27
Post charge current Percentage
%
note(22)
28
Equalize safety time (Eq T security)
Hours
note(22)
29 Unused
30
Rectifier high volts alarm level
Volt
note(1)
31
Battery high volts alarm level
Volt
note(1)
32 Rectifier
low
volts level
Volt
note(1)
33
Battery low volts level
Volt
note(1)
34
High volts shutdown level
Volt
note(1)
35
End of Discharge level
Volt
note(1)
36
Negative Ground fault alarm level
Mili Ampere
note(1)
37
Positive ground fault level
Mili Ampere
note(1)
38
Control board & inside high temperature level
°C
note(22)
39
Battery high temperature level
°C
note(22)
40
Battery low temperature level
°C
note(22)
41
AC high volts alarm level
Volt
note(1)
42
AC low volts alarm level
Volt
note(1)
43
High DC current rectifier level
Ampere
note(1)
44
Low DC current rectifier level
Ampere
note(1)
45
High ripple alarm level
%
note(1)
46
Cell failure alarm level
Volt
note(1)
47
High DC current battery level
Ampere
note(1)
48
Low DC current battery level
Ampere
note(1)
Summary of Contents for ARR-M Series
Page 2: ... i BATTERY CHARGER USER S MANUAL ...
Page 5: ... iv FIGURE LIST 86 ACRONYM LIST 88 LCD MESSAGES LIST 90 APPENDIXES 92 ...
Page 6: ...MCEnPC23 REV 2 4 Page 1 PART 1 INSTALLATION INSTALLATION ...
Page 10: ...MCEnPC23 REV 2 4 Page 5 PART 2 THEORY OF OPERATION THEORYOFOPERATION ...
Page 98: ...Page 1 of 39 Rev 13 Communication User Manual Appendix 3 27 01 2015 ...