Page 36 of 39
Rev. 13
15 14 13 12 11 10
9
8
7
6
5
4
3 2 1
0
0: Battery high volts
1: Rectifier high volts
2: High volts shutdown
3: Battery low volts
4: Rectifier low volts
5: Low volts disconnect
6: Negative ground fault
7: Positive ground fault
8: Rectifier fail
9: Internal high temperature
10: Internal low temperature
11: Battery high temperature
12: Battery low temperature
13: AC high volt
14: AC low volt
15: x
This register is used to enable or disable any of the above alarms.
Note 16
Alarm latch relay authorization address: (2D hex)
15 14 13 12 11 10
9
8
7
6
5
4
3 2 1
0
0: Battery cell failure
1: AC fail
2: High ripple
3: High DC current
4: Low DC current
5: Equalize alarm
6: Mains frequency failure
7: Battery test failure
8: High current battery
9: Low current battery
10: High capacity
11: Low capacity
12: x
13: x
14: Common alarm
15: x
This register is used to enable and disable the above alarm relay latching.
Note 17
Alarm latch message authorization address: (2E hex)
15 14 13 12 11 10
9
8
7
6
5
4
3 2 1
0
0: Battery high volts
1: Rectifier high volts
2: High volts shutdown
3: Battery low volts
Summary of Contents for ARR-M Series
Page 2: ... i BATTERY CHARGER USER S MANUAL ...
Page 5: ... iv FIGURE LIST 86 ACRONYM LIST 88 LCD MESSAGES LIST 90 APPENDIXES 92 ...
Page 6: ...MCEnPC23 REV 2 4 Page 1 PART 1 INSTALLATION INSTALLATION ...
Page 10: ...MCEnPC23 REV 2 4 Page 5 PART 2 THEORY OF OPERATION THEORYOFOPERATION ...
Page 98: ...Page 1 of 39 Rev 13 Communication User Manual Appendix 3 27 01 2015 ...