9-6
PowerWAVE 9000 DPA UPS - Options
(Issue 2.1 Oct. 2009)
shut down or informing connected users. The shut down procedure can be
initiate from the remaining time (downtime) or as countdown timer from
the beginning of the alarm. A shut down is therefore possible without extra
input from the operator, but fully software controlled.
The External SNMP adapter is small,
12 x 7 cm. and is supplied with the
following accessories:
1.
RJ-45 connector for 10/100
Base-T (autoswitchable)
2.
Serial Port (COM2) or optional
ModBus interface.
3.
Error/Link LED for UPS status
4.
Aux Port
5.
DIP Switch
6.
Serial Port to the UPS (COM1)
7.
DC Supply (9 VDC or 9-36 VDC supply, depending on model);
Figure 9.5: External SNMP Adapter
.The Internal SNMP-Card can also
be inserted into an appropriate
expansion slot in the PowerWAVE
9000 Modules or Cabinet.
This adapter communicates via the
serial port of the UPS and makes a
direct multiple server shut down
possible without additional SNMP
management software.
Figure 9.6: Internal SNMP Adapter
For detailed information please refer to the Software Manual provided with
the WAVEMON CD ROM. This adapter communicates via the serial port
of the UPS and makes a direct multiple server shut down possible without
additional SNMP management software.
RCCMD - Remote Console Command module
for a multi-server
shutdown. The RCCMD modules are independent programs that may be
activated on the computer that is running UPSMAN. This makes a
shutdown call possible in any LAN and WAN, regardless of the network
type or operating system.