8
Overall dimensions (mm)
*L = measure referred to burner provided with extended blast tube
Performance Curves
To get the input in kcal/h, multiply value in kW by 860.
Data are referred to standard conditions: atmospheric pressure at 1013mbar, ambient temperature at 15°C
NOTE:
The performance curve is a diagram that represents the burner performance in the type approval phase or in the laboratory
tests, but does not represent the regulation range of the machine. On this diagram the maximum output point is usually reached by adj-
suting the combustion head to its “MAX” position (see paragraph “Adjusting the combustion head”); the minimum output point is rea-
ched setting the combustion head to its “MIN” position. During the first ignition, the combustion head is set in order to find a
compromise between the burner output and the generator specifications, that is why the minimum output may be different from the Per-
formance curve minimum.
Burner flange and boiler
recommended drilling tem-
plate
AS
AL
AD
B
BL
C
CL
D
E
F
G
H
II
K
L
M
N
O
O
P
T
min.
Z
W
min. - max.min. - max.min. - max.min. - max.
min. max.
G6
345
455
12
53 - 67
53 - 177
278 - 292 278 - 402
375
65
310
Ø80
Ø101
x
162 187 M8 156 86
138 112
x
80
265
G10
352
472
12
81
201
270
270
375
33
342 Ø88,9 Ø125 Ø105 160 221 M8 170 109 131 120 18 80
311
G18
352
472
12
81
201
270
270
375
33
342 Ø114,3 Ø134
x
160 221 M8 170 109 131 120 18 80
311
BACK PRE
SSURE
IN
COMBU
S
TION CHAMBER mb
ar
kW
0
0,2
0,4
0,6
0,8
1
1,2
1,4
10
30
50
70
90
110 130 150 170 190 210 230
G6
G10
G18