7
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Specifications
NOTE:
Choosing the nozzle for light oil, consider Hi equal to 10210 kcal/kg.
* NOTE ON THE WORKING SERVICE: for safety reasons, one controlled shutdown must take place every 24 hours of conti-
nuous working.
Type
G10
Model
G-. TN. S. *. Y.
(1) (2) (3) (4) (5) (6)
(1)
BURNER TYPE
G6 - G10 - G18
(2)
FUEL
G -
Light oil
(3)
OPERATION
TN -
Single stage
(4)
BLAST TUBEBLAST TUBE
S -
Standard
L -
Extended
(5)
DESTINATION COUNTRY
* - see data plate
(6)
BURNER VERSION
Y -
Special version (24Vdc power supply)
BURNER TYPE
G6
G10
G18
Output
min. -max. kW
29 - 70
58 - 116
105 - 209
Fuel
Light oil
Light oil rate
min. - max. kg/h
2.5 - 6
5 - 10
9 - 18
Light oil viscosity
cSt @ 40°C
2 - 7.4
Light oil density
kg/m
3
0.84
Power supply
24 Vdc
Motor
Двигатель
W
110
180
180
Total power consumption
W
210
280
280
(approx.)Weight kg
15.5
17
18
Operation
Single-stage
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60