Installation diagram of light oil pipes
PLEASE READ CAREFULLY THE “WARNINGS” CHAPTER AT THE BEGINNING OF THIS MANUAL.
The pumps that are used can be installed both into single-pipe and double-pipe systems.
Single-pipe system:
a single pipe drives the oil from the tank to the pump’s inlet. Then, from the pump, the pressurised oil is driven to
the nozzle: a part comes out from the nozzle while the othe part goes back to the pump. In this system, the by-pass pulg, if provided,
must be removed and the optional return port, on the pump’s body, must be sealed by steel plug and washer.
Double-pipe system:
as for the single pipe system, a pipe that connects the tank to the pump’s inlet is used besides another pipe that
connects the pum’s return port to the tank, as well. The excess of oil goes back to the tank: this installation can be considered self-ble-
eding. If provided, the inside by-pass plug must be installed to avoid air and fuel passing through the pump.
Burners come out from the factory provided for double-stage systems. They can be suited for single-pipe system (recommended in
the case of gravity feed) as decribed before.
To change from a 1-pipe system to a 2-pipe-system, insert the by-pass plug
G
(as for ccw-
rotation- referring to the pump shaft).
Caution:
Changing the direction of rotation, all connections on top and side are reversed.
To convert an A/AD pump from two-pipe to one-pipe operation, proceed as follows:
1 remove the 1/8” plug from the vaccum port.
2 using a 2,5 mm Allen wrench, unsrew the by-pass plug from the vaccum gauge port (see Fig. 8-A)
3 screw back the 1/8” plug in the vaccum port
4 insert and screw a 1/4” plug into the return port (see Fig. 8-B).
Fig. 8
Fig. 7 -
Double-pipe system
The burner is supplied with filter and flexible hoses, all the parts upstream the filter and downstream the return flexible hose,
must be installed by the customer. As far as the hoses connection, see the related paragraph.
Key
1
Burner
2
Flexible hoses (fitted)
3
Light oil filter (fitted)
4
Automatic interceptor (*)
5
One-way valve (*)
6
Gate valve
7
Quick-closing gate-valve (outside the tank or boiler rooms)
(*) Only for installations with gravity, siphon or for-
ced circulation feed systems. If the device installed
is a solenoid valve, a timer must be installed to
delay the valve closing.
The direct connection of the device without a timer
may cause pump breaks.
From tank
To tank
A
B