Terminal
group
Connection symbol
Input
Out
pu
t
Description of connection terminals
Electrical rating
X5-01
PIN1
x
Protective
earth
(PE)
PIN2
x
Pressure switch min-oil (DWmin-oil)
AC 230 V +10 % / -15 %,
50...60 Hz, Imax 1.5 mA
PIN3
x
Power signal for pressure switch-min-
oil (DWmin-oil)
AC 230 V +10 % / -15 %,
50...60 Hz, Imax 500 mA
X5-02
PIN1
x
Protective
earth
(PE)
PIN2
x
Pressure
switch-max-oil
(DWmax-oil)
AC 230 V +10 % / -15 %,
50...60 Hz, Imax 1.5 mA
PIN3
x
Power signal for pressure switch-max-
oil (DWmax-oil)
AC 230 V +10 % / -15 %,
50...60 Hz, Imax 500 mA
X5-03
PIN1
x
Controller (ON / OFF)
AC 230 V +10 % / -15 %,
50...60 Hz, Imax 1.5 mA
PIN2
x
Controller closes / stage 3
AC 230 V +10 % / -15 %,
50...60 Hz, Imax 1.5 mA
PIN3
x
Controller opens / stage 2
AC 230 V +10 % / -15 %,
50...60 Hz, Imax 1.5 mA
PIN4
x
Power signal for control of con- troller AC 230 V +10 % / -15 %,
50...60 Hz, Imax 500 mA
X6-01
PIN1
x
Start release oil
AC 230 V +10 % / -15 %,
50...60 Hz, Imax 1.5 mA
PIN2
x
Power signal start release oil
AC 230 V +10 % / -15 %,
50...60 Hz, Imax 500 mA
PIN3
x
Direct heavy oil start
AC 230 V +10 % / -15 %,
50...60 Hz, Imax 1.5 mA
PIN4
x
Power signal direct heavy oil start
AC 230 V +10 % / -15 %,
50...60 Hz, Imax 500 mA
X6-02
PIN1
x
Protective
earth
(PE)
PIN2
x
Neutral conductor (N)
PIN3
x
Oil pump / magnetic coupling
AC 230 V +10 % / -15 %,
50...60 Hz, 2 A, cos.0.4
X6-03
PIN1
x
Protective
earth
(PE)
PIN2
x
Neutral conductor (N)
PIN3
Fuel valve (shutoff valve-oil)
AC 230 V +10 % / -15 %,
50...60 Hz, 1 A, cos.0.4
Summary of Contents for C120A
Page 46: ......
Page 47: ......
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......