32
10.3 Setting the special positions
1st level
2nd level
3rd level
4th level
5th level
6th level
Description
Param & Display
RatioControl
GasSettings
OilSettings
SpecialPosition
Suggested positions are below. They can be modify during the commissioning according to right needs.
Special Position: AUX3 POS
•
Home position
0° (Closed)
•
Prepurge position
90° (Open)
•
Ignition position
0° (Closed)
•
Postpurge position
90° (Open)
10.4 Setting the load controller mode: see the previous chapter (regolazione senza FGR)
WARNING: If one of the intLC (internal Load Controller) option must be choice, a temperature sensor cannot be connected to the
terminal X60. A temperature sensor with analogue output or a converter Ohm
Æ
mA or V must be used. They must be connected
to the terminals X61.
WARNING: If one of the extLC (External Load Controller) options must be used, set “no sensor”, "Temperature sensor" or
"Pressure Sensor" on the choice for the modulation probe.
WARNING: The X61 door must be configured in according to the used sensor or signal.