PART I: SPECIFICATIONS
5
BURNERS FEATURES
Gas operation:
From the supply line the gas fuel passes through the gas train (filter, safety valves, gas pressure regulator and butterfly
valve). The pressure regulator sets the gas pressure within the combustion head utilization limits. Air is supplied by a fan, which may be
onboard or separated depending on burner configuration, and is channeled through an air damper.
The air damper and the gas butterfly valve are actuated by servomotors according to load curves, in order to achieve the correct
proportion between fuel and air flows, and to optimize flue gas parameters.
The adjustable combustion head can improve the burner performance by controlling the flame geometry and combustion efficiency.
Fuel and air are routed through separated channels inside the combustion head, then mixed to ignite the flame inside the combustion
chamber. The ignition spark is provided by electrodes and a high voltage transformer (a pilot flame may also be employed, depending
on burner configuration).
Pre-ventilation of the combustion chamber is usually implemented according to gas directives.
The control panel, onboard or separated, allows the operator to monitor each operating phase.
PART I: SPECIFICATIONS
2
Burner with ABS polymer (silenced) air inlet
Burner with aluminium air inlet
3
4
6
5
7
8
1
11
10
9
7
Note: the figure is indicative only
1
Control panel with startup switch
2
Gas valve group
3
Electrical panel
4
Cover
5
Blast tube + Combustion head
6
Flange
7
Actuator
8
Silcencer
9
Air pressure switch
10 Head adjusting ring nut
11 Fan motor
Summary of Contents for C120A
Page 46: ......
Page 47: ......
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......