Burners are identified by burner type and model. Burner model identification is described as follows.
Fuel
The burner technical specifications, described in this manual, refer to natural gas (calorific net
value Hi = 9.45 kWh/Stm
3
, density
ρ
= 0.717 Kg/Stm
3
). For different fuel such as LPG, town gas
and biogas, multiply the values of flow and pressure by th corrective factors shown in the table
below.
For example, to obtain the flow and pressure values for the biogas:
Type
C85A
Model
M-.
MD. SR.
*.
A. 1.
80.
ES.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
1 BURNER TYPE
C85A, C120A
2 FUEL
M - Natural gas
B - Biogas
L - LPG
3 OPERATION (Available versions)
PR - Progressive
MD - Fully modulating
4 BLAST TUBE AND AIR INLET CONFIGURATION
(see picture on page 5)
SR = Standard blast tube + ABS polymer (silenced) air intake
SP = Standard blast tube + aluminium air intake
LR = Extended blast tube + ABS polymer (silenced) air intake
LP = Extended blast tube + aluminium air intake
5 DESTINATION COUNTRY
* - see data plate
6 BURNER VERSION
A - Standard
Y - Special
7 EQUIPMENT
0 = 2 gas valves
1 = 2 gas gas proving system
7 = 2 gas maximum gas pressure switch
8 = 2 gas gas proving maximum gas pressure switch
8 GAS CONNECTION
see Specifications
32 = Rp1
1/4
40 = Rp1
1/2
50 = Rp2
65 = DN65 80 = DN80
9 MICRO-PROCESSOR CONTROL
ES = with no O
2
trim control, with no VSD control
EO = with O
2
trim control, with no VSD control
EI = with no O
2
trim control, with VSD control
WARNING! The burner must be used only with the fuel specified in the burner data
plate .
Fuel
Hi
(KWh/Stm
3
)
ρ
(kg/Stm
3
)
f
Q
f
p
LPG
26,79
2,151
0,353
0,4
Town gas
4,88
0,6023
1,936
3,3
Biogas
6,395
1,1472
1,478
3,5
ATTENTION! The combustion head type and the settings depend on the fuel. The burner must be used only for its
intended purpose specified in the burner data plate .
ATTENTION! The corrective factors in the above table depend on the gas composition, so on the calorifc value and
the density of the gas. The above value can be taken only as reference.
Type --
Model
--
Year --
S.Number --
Output --
Oil Flow
--
Fuel
--
Category --
Gas Pressure
--
Viscosity --
El.Supply --
El.Consump. --
Q
biogas
Q
naturalGas
1 478
=
p
biogas
p
naturalGas
3 5
=
Summary of Contents for C120A
Page 46: ......
Page 47: ......
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......