
PART I: SPECIFICATIONS
10
How to read the burner “Performance curve”
To check if the burner is suitable for the boiler to which it must be instal-
lled, the following parameters are needed:
furnace input, in kW or kcal/h (kW = kcal/h / 860);
backpressure (data are available on the boiler ID plate or in the
user’s manual).
Example:
Furnace input: 600kW
Backpressure: 4mbar
In the “Performance curve” diagram, draw a vertical line matching the
furnace input value and an horizontal line matching the backpressure
value. The burner is suitable if the intersection point A is inside the per-
formance curve.
Data are referred to standard conditions: atmospheric pressure at
1013mbar, ambient temperature at 15°C.
Performance Curves
To get the input in kcal/h, multiply value in kW by 860.
Data are referred to standard conditions: atmospheric pressure at 1013mbar, ambient temperature at 15° C
NOTE:
The performance curve is a diagram that represents the burner performance in the type approval phase or in the laboratory tests, but does not
represent the regulation range of the machine. On this diagram the maximum output point is usually reached by adjsuting the combustion head to its
“MAX” position (see paragraph “Adjusting the combustion head”); the minimum output point is reached setting the combustion head to its “MIN” position.
During the first ignition, the combustion head is set in order to find a compromise between the burner output and the generator specifications, that is why
the minimum output may be different from the Performance curve minimum
Gas pressure in combustion
h
ead
C85A M-..
Stm
3
/h
C120A M-..
Stm
3
/h
Gas pressure in co
mb
ustion he
ad
C120A L-..
Stm
3
/h
Campo di lavoro bruciatori
Tipo P60 Mod. M-xx.x.IT.A.0.50 - M-.xx.x.IT.A.0.65
-1
0
1
2
3
4
5
6
7
8
100
200
300
400
500
600
700
800
900
Potenza kW
Contropressione in camera di
combustione mbar
A
ba
ckpr
essu
re in
co
m
bu
st
ion
ch
am
b
e
r
(m
b
ar
)
Power kW
Summary of Contents for C120A
Page 46: ......
Page 47: ......
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......