22
Condensation drain
The boiler, during the combustion process, produces conden-
sation that, through pipe “A”, flows into the trap.
The condensation that forms inside the boiler flows
into a suit-
able drain via pipe “B”.
Danger!
Before commissioning the appliance:
- check that the siphon is assembled correctly
- fill the siphon through the filler cap “C” and
check correct drainage of the condensate
If the appliance is used with an empty conden-
sation drain trap, there is an intoxication hazard
due to the release of exhaust gases.
The connection between the appliance and the
domestic wastewater system must be made in
compliance with the specific reference standards.
H min 100 mm
150
C
A
B
150**
25*
If you do not want to or cannot create a base,
the boiler can be mounted at ground level and
a sump at least 100 mm deep can be made to
house the siphon
BoIler room
floor
To The
condenSATe
drAIn
The upper generator
of the drain pipe
must not be higher than
the bottom of the pan.
NOTE!
For further details
refer to the Technical Information
from the website
* minimum safety siphon set by the standard
** minimum head with boiler running at maximum power.
FRONT sIDE
The outlet of the condensate drainage pipe is towards the con-
nection side of the flue gas box manifold, removing the pre-cut
part on the covering panel.