15
Technical Features
ENGLISH
eXAmPle:
For a ∆T 20K, of a MODULEX 250, the maximum
water flow rate required is 10514 l/h.
The graph of the boiler pressure drops shows that
the pump must ensure a head of at least 1.6 m/h
2
o
NOTE:
It is always advisable to use a hydraulic separator (*) between
the boiler circuit and the system.
FLOw RATE l/h
Pressure drop (m
h
2
O)
2.4.2 - DETERMINATION OF ThE PRIMARY CIRCUIT PUMP OR BOILER PUMP
The pumps must be determined by the installer
or designer according to the boiler and sys-
tem data.
The boiler pump must have head that is able to ensure the
pump's flow rates according to the circuit's
∆
t.
MODULEX EXT 100
Maximum flow rate in l/h (
∆
t=15K)
5,573
Requested rated flow rate in l/h (
∆
t=20K)
4,180
MODULEX EXT 250
Maximum flow rate in l/h (
∆
t=15K)
14,018
Requested rated flow rate in l/h (
∆
t=20K)
10,514
MODULEX EXT 116
Maximum flow rate in l/h (
∆
t=15K)
6,471
Requested rated flow rate in l/h (
∆
t=20K)
4,853
MODULEX EXT 300
Maximum flow rate in l/h (
∆
t=15K)
16,856
Requested rated flow rate in l/h (
∆
t=20K)
12,642
MODULEX EXT 150
Maximum flow rate in l/h (
∆
t=15K)
8,376
Requested rated flow rate in l/h (
∆
t=20K)
6,282
MODULEX EXT 350
Maximum flow rate in l/h (
∆
t=15K)
19,712
Requested rated flow rate in l/h (
∆
t=20K)
14,784
MODULEX EXT 200
Maximum flow rate in l/h (
∆
t=15K)
11,192
Requested rated flow rate in l/h (
∆
t=20K)
8,394
The pump is not an integral part of the boiler.
It is recommended to select a pump with a flow rate
and head of approximately 2/3 of its characteristic
curve.
(*)
for the features, refer to the
sPINOX
installation manual, available on the website.