12
The
D
t between supply and return boiler must
never be less than 15 ° K.
NOTE:
The use of a mixing header fitted between the
boiler circuit and the system circuit is always ad-
visable. It becomes INDISPENSABLE if the sy
-
stem requires flow rates superior to the maximum
permitted boiler flow rates, which is to say lower
than 20 K.
2.4 - dIAGRAM OF FlOW RATE/PRESSURE AVAIlABlE FOR InSTAllATIOn
Flow rate (l/h)
Avaible Head (m.c.a.) metres of water
The table provides an indication the flow the pump in function of the
D
t of the primary circuit.
KON 100
KON 115
Power supply
kW
99,5
115
Max flow rate demanded (
D
t 15 K)
l/h
5700
6600
Nominal flow rate request (
D
t 20 K)
l/h
4280
4950
Power supply in condensation (50/30) kW
105
120,3
Max flow rate demanded (
D
t 15 K)
l/h
6020
6897
Nominal flow rate request (
D
t 20 K)
l/h
4520
5173