3.13 - COMMISSIONING
Preliminary checks before start-up
The installation, operation and maintenance
must be carried out in compliance with the
regulations in force, following the instruc-
tions described in this manual; also, any op-
eration must be carried out by professionally
qualifi ed and authorised personnel.
ATTENTION!
ANY INTERVENTION ON THE APPLIANCE
MUST BE DONE BY QUALIFIED PERSON.
IT IS STRICTLY FORBIDDEN FOR PERSONS
NOT SPECIFICALLY ENABLED TO USE, RUN,
MAINTENANCE THE APPLIANCE.
AFTER CONNECTING THE HYDRAULIC AND ELECTRICAL SYSTEM AND THE FUEL LINE TO THE GENERATOR,
AND BEFORE STARTING UP THE GENERATOR, CHECK THE FOLLOWING:
have the hydraulic and electrical systems and fuel been connected in compliance with the domestic and local laws
in force and as indicated in this manual
?
are the electrical components of the generator wired correctly?
are the connections tightened?
are the network frequency and voltage compatible with the generator control panel (400V 3F+N+E)?
Are the combustion air intake line and the fl ue gas evacuation line compliant with the applicable standards in
force?
Are the ventilation conditions and minimum distances to perform any maintenance guaranteed?
Are the refractory coverings intact?
is the furnace free of foreign bodies?
has the door been tightened correctly?
is the burner assembled according to the instructions in the manufacturer's manual and has the burner blast tube
infi ll been performed correctly?
have the electrical connections of the safety devices on the burner been done correctly?
the fuel feed system is dimensioned
according to the fl ow rate required for the generator and is provided with all
safety and control systems prescribed by current standards?
does the fuel to be used correspond to the burner calibration fuel?
is the fuel supply valve open?
has the system been checked for fuel leaks?
are the fi lling unit valves in operating position?
are the vent and drain valves closed?
are the circuit shut-off valves open?
is the motor shaft of the pump(s) free to rotate regularly when turning it by hand?
is the pump joint alignment correct?
do the electric motors (pumps and burner) have the correct direction of rotation?
has the operator been trained and provided with the documentation?
Please tick the operations performed