36
(SE) Service parameters
ACTIVATION - SELECTION See section 1 (4.2)
Press reset buton
(D)
to access the SE parame-
ters unit. These parameters can be edited with-
out restrictions, from the control panel.
DISPLAY
Turn knob (
B)
to display the parameters list
2
PARAMETERS LIST SE
CODE RANGE DESCRIPTION
Po
0
1
Post circulation
0 = post 5’’ (default)
1 = continuous
oC
-20 10
External probe on panel
- 20÷10 °C
(default -10)
0 30
External probe on Regolafacile
0 = - 20 °C
30 = +10 °C (default 10)
nr
0/5 30
Night reduction
0 = T.A. (default)
5 ÷ 30 = night reduction
PH
0
1
Domestic hot water pre-
heat function
0 = Not active (default)
1 = Active
HP
0 100
Maximum heating modula-
tion level (default 100)
HL
20 50
Minimum heating set point
level (default 30)
HH
50 85
Maximum heating set point
level (default 85)
dL
25 45
Minimum domestic hot water
set point level (default 35)
dH
50 65
Maximum domestic hot water
set point level (default 60)
EDITING THE VALUE
Press reset buton
(D)
to access the parameter,
the parameter value flashes.
Correct the value with knob
(C)
(Counterclockwise - Clockwise)
4 CONFIRM VALUE
Press key
D
3
4