3.11 - MEASUREMENT OF COMBUSTION EFFICIENCY DURING INSTALLATION
ATTENTION!
Function reserved for Authorised
Assistance Centres only.
3.11.1- ACTIVATION OF THE CALIBRATION FUNCTION
1
ACTIVATION
By pressing the button (
D
) for 5 seconds, until
SErvice appears,
Do not press it for more than
9’’ (par. 4.2)
This function is not activated if there is
a block or domestic hot water request .
It is pos-
sible to dispose of heat on the sanitary circuit by
opening 1 or more hot water taps.
all the symbols on the display flash
2
MAXIMUM OUTPUT
By turning the knob (B) onto MAX, the boiler will
operate at
maximum output:
- 1 lluminated symbol
When the high flame symbol is fixed on the display
and there is an alternation between
SP
and flow
temperature, the boiler operates at maximum
power.
Make combustion efficiency
4
DISABLING
The “calibration” function stays active for 15 min
-
utes.
To disable the
CALIBRATION
function before the
time elapses press the button
(D)
for 5 seconds
until the ‘SERVICE’ symbol appears
and then release. Do not press for more than
9 seconds.
3
MINIMUM OUTPUT
By turning the knob (B) in position , the boiler
will operate at
minimum output
:
- 1 lluminated symbol
and there is an alternation between
SP
and flow
temperature, the boiler operates at minimum
power.
Make combustion efficiency
x 5’’
The user is NOT authorised to activate
the function described below.
MAX
M
IN
MAX
M