Spindle Out Of Sequence
Spindle arm indexed to an unexpected position. Check
spindle alignment prox and/or servo drive programming.
R0181
Spindle Up Cmd. Failed
Spindle up command failed. Spindle was sent up; but
the up position prox was never detected. Check the up
position prox switch. If cylinder still down check PLC
output X4 for voltage, and up solenoid valve. Also
check machine has air pressure.
R0191
Spindle Up/Down Prox On
Spindle up & down sensors are both on at the same
time. The sensor that is activated that should not be is
stuck on.
R018C Tray 1 Failed To Move
Check that tray 1 is not blocked from moving. Tray stop
1 actuator is working; tray 1 sensor is not stuck on.
R018B
Tray 2 Failed To Move
Check that tray 2 is not blocked from moving. Tray stop
2 actuator is working; tray 2 sensor is not stuck on.
R018A
Tray 3 Failed To Move
Check that tray 3 is not blocked from moving. Tray stop
3 actuator is working; tray 3 sensor is not stuck on.
R0189
Tray 4 Failed To Move
Check that tray 4 is not blocked from moving. Tray stop
4 actuator is working; tray 4 sensor is not stuck on.
R0197
UV Lamp Extended Prox
Failed
Failed to detect the "extended" prox when cycling the
lamp. Check the "extended" prox switch. Adjust prox
switch to read lamp.
R0192
UV Lamp Home Prox Failed Failed to detect the "home" prox when cycling the lamp.
Check the "home" prox switch. Adjust prox switch to
read lamp.
R0193
UV Lamp Lost Power
UV lamp intensity did not meet/exceed set point during
curing cycle. Check UV lamp and sensor.
R0208
UV Lamp Not Moving
The lamp is not moving off of the prox switch. Check
both prox switches. Also check that lamp motor is
moving.
R0039
UV Lamp Test Failed
UV lamp has failed to reach proper intensity during
start-up on 10 consecutive attempts. Check UV lamp
and sensor.