Install the 2000DX in a position where ventilation ducts can be easily run to each of the
four duct connection points and there is adequate room to access each door on the unit for
maintenance purposes. (See Airflow Diagrams for duct connection locations and airflow
designations, these are also labeled on the unit.) It is recommended that there be at least
36” of clearance at each duct connection point to ensure there is enough room to remove
the doors. To facilitate easy duct removal for maintenance, make a portion of each duct
section, 24” to 36”, easily removable.