When the RecoupAerator is wired directly to the optional CO2 monitor, the air flow will be
controlled by the CO2 level input. The CO2 monitor will respond approximately as follows:
<800 ppm CO2:
lo flow
240 CFM
800-1000 ppm CO2:
med flow
720 CFM
1000-1200 ppm CO2:
med hi flow
1210 CFM
>1200 ppm CO2:
hi flow
1795 CFM
The control will default to the higher flow position – being the command from the CO2
monitor or via the dial control.
The RecoupAerator is EconoCool-equipped, so that you can make use of outside air in
summer (e.g., during the night) to cool your building, thereby providing AC energy savings.
Using a temperature sensor on the incoming air stream and a sensor on the room
temperature, the RecoupAerator
automatically stops energy recovery at some preset
certain conditions. The user can select between the presets by changing JP2~JP6.