SIT/SDS Series

                                         

DIGITAL DIFFERENTIAL PRESSURE SWITCH & TRANSMITTER

Copyright 

ⓒ 

2003.08  ULFA  TECHNOLOGY  CO.,LTD                                                    http://www.ulfatech.com

4

   

Function

Setting and Calibration

Zero setting :

 Optimize display and current out to 

zero automatically by front key pressed.

Peak pressure Measurement :

 This mode is 

display for peak pressure by supplied pressure.  And 

the display is cleared by press enter key in the peak 

mode. 

Offset(

p) pressure Measurement :

 This 

mode is display the changed pressure based on the 

current pressure. Current pressure is turned into "0" 

when offset mode selected. This mode does not 

concern to 4-20mA current out put.

Sampling time setting :

 Sample rate is 0.1sec of 

this product. Sampling time is measuring time by 

sample rate. For example, if setting time is 2 sec, 

SIT/SDS measures 20 times for 2 seconds and out 

to display and 4-20mA out put by average of 20 

times measured value.

Switch :

 SIT/SDS has two switches output. Each 

switch operate individually and has A(normal open) 

and B(normal close) contacts. 

Transmitter(SIT) :

 SIT/SDS has 4-20mA current 

out put. Span (20mA) range can be changed within 

original range.

Communication(option) : 

Measurement pressure 

can be sent by RS232 or RS485 for option 

specification.

ID setting :

 This mode set identification number for 

communication. 

Over pressure warning :

 SIT/SDS displays 

warning on segment for over pressure (positive and 

negative). Upper 4 elements of 7segment("

―  ―  ―  ―

") 

blink for warning when measurement pressure over 

10% for high pressure(factory setting value), And 

under 4 elements of 7segment("_ _ _ _") blink for 

warning when measurement pressure under 10% for 

low pressure(factory setting value), 

Factory setting recovery :

 The parameters are 

changed all to factory setting value and all user 

setting value is cleared.

Hear by describe key function and setting methode.
Please read this section carefully for the correct and 
optimum use of this product.

UP

DOWN

MODE

ENTER

             

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

Key functions

Peak mode

Offset mode

- Increase setting value
- Offset mode set/reset

- Decrease setting value
- Peak pressure mode set/reset

- Entering into the setting mode
- Setting item circulation

- Save setting value
- Clear peak value in the peak mode
- Release setting mode

 

Press the PEAK(down) 
key once to set peak 
mode 

"PEA" displayed like left 
while press peak key

Press the ENTER to 
reset peak value and 
newly start

Press the PEAK(down) 
key once more to release 
peak mode 

             

Press the 

P(UP) key 

once to set offset mode

"dELt" displayed like left
while press 

P key

Press the 

P(UP) key

P

PK

S1

S2

Summary of Contents for SIT Series

Page 1: ...R Copyright ⓒ 2003 08 ULFA TECHNOLOGY CO LTD http www ulfatech com 1 Instruction Manual Digital Differential Pressure Switch Transmitter 1 General Specification 2 Installation 3 Wiring 4 Function 5 Setting Calibration 4 Digit Display 4 20mA Output 2 Level Control ...

Page 2: ...C 50 60Hz Connections 2 screw terminal block Display 4 Digit LED Warm up Time 15 minutes SWITCH Relay Contact 2 SPDT NC COM NO Contact Rating 1A 30VDC 0 5A 125VAC Connections 6 Screw terminal block Level setting Individual level setting Switch 1 2 TRANSMITTER SIT Range Table Connections 2 Screw terminal block Output Signal 4 20mADC limited at 30mADC Model No Range Resolution Loop Resistance 0 1100...

Page 3: ...he power specification is DC24V or AC220V 2 Verify that the facility s main power source is turned off or disconnected 3 Connect lead cable to power terminal matching polarity as shown in FIG 2 below Take care that wrong wiring will damage the Instrument and malfunction AC220V is not concerned to polarity CURRENT OUT CONNECTION 4 20mA SIT only The SIT sends a standard 2 wire 4 20mA current out 1 C...

Page 4: ...sent by RS232 or RS485 for option specification ID setting This mode set identification number for communication Over pressure warning SIT SDS displays warning on segment for over pressure positive and negative Upper 4 elements of 7segment blink for warning when measurement pressure over 10 for high pressure factory setting value And under 4 elements of 7segment _ _ _ _ blink for warning when meas...

Page 5: ...to measure mode Press ENTER for more than 3 seconds to save and exist in the switch level setting mode SWITCH2 OFF LEVEL Switch level setting Press MODE key to select sw2 off level set mode S2 LED is on while into the sw2 off level setting mode 2oFF displayed like left while press mode key in the sw2 off level setting mode Set your switch level use up down key Press ENTER once to save and exit to ...

Page 6: ...sure 20 times for 2 seconds and calculate average of measured 20 data to display and 4 20mA current output This functions is useful to measure hunted pressure Press MODE key for more than 3 seconds till sw1 LED is on and appear Int on segment display like left Release MODE key then appear current set time on segment display default set time is 0 5 sec Set your sampling time use up down key Press E...

Page 7: ...zero span etc Press MODE key for more than 3 seconds till appear Int on segment display Press MODE key once till appear FACt on segment display Press ENTER once to recall and exit to measure mode Press ENTER key for more than 3 seconds till appear SAvE on segm ent to recall and exist in the setting mode ID No setting ID number is use for address for communication to master It s concern to SIT SDS ...