PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

SIT/SDS Series

                                         

DIGITAL DIFFERENTIAL PRESSURE SWITCH & TRANSMITTER

Switch level setting

Press the MODE key once to change switch setting 
level. The setting mode circulate <SW1 OFF 

⇒ 

SW1 

ON 

⇒ 

SW2 OFF 

⇒ 

SW2 ON> when mode key 

press repeated. Switches can be use to below  two 
type by level setting.

(1) Hysteresis mode

(2) Window mode

CAUTION

① 

On level = Off level :  switch  off

② 

It is necessary to differ On level and Off level  

   above 4digits.

Press MODE key once to 
set sw1-off level.  
S1 LED is on while into 
the sw1-off level setting 
mode
"1oFF" displayed like left 
while press mode key in 
the sw1-off level setting 
mode

Set  your switch level use 
up/down key

Press ENTER once to 
save and exit to measure 
mode. Press ENTER for 
more than 3 seconds to 
save and exist in the 
switch level setting mode

SWITCH1 OFF LEVEL

SWITCH1 ON LEVEL

Press MODE key to select 
sw1-on level set mode. 
S1,

P LED is on while 

into the sw1-on level 
setting mode
"1on" displayed like left while 
press mode key in the 
sw1-on level setting mode

Set  your switch level use 
up/down key
Press ENTER once to 
save and exit to measure 
mode. Press ENTER for 
more than 3 seconds to 
save and exist in the 
switch level setting mode

SWITCH2 OFF LEVEL

Switch level setting

                       
         
                                 

Press MODE key to select 
sw2-off level set mode. 
S2 LED is on while into 
the sw2-off level setting 
mode
"2oFF" displayed like left 
while press mode key in 
the sw2-off level setting 
mode

Set  your switch level use 

up/down key

Press ENTER once to 
save and exit to measure 
mode. Press ENTER for 
more than 3 seconds to 
save and exist in the 
switch level setting mode

SWITCH2 ON LEVEL

Press MODE key to select 
sw2-on level set mode. 
S2,PEAK LED is on while 
into the sw2-on level 
setting mode
"2on" displayed like left 
while press mode key in 
the sw2-on level setting 
mode
Set  your switch level use 
up/down key

Press ENTER once to 
save and exit to measure 
mode. Press ENTER for 
more than 3 seconds to 
save and exist in the 
switch level setting mode

User setting mode

Entering User setting mode :

 Pres  

MODE key for more than 3seconds till appear "I n t" 
on segment into the user setting mode. Press th

s

e

MODE key once in user setting mode to change 
setting item. The setting item circulate " I n t " 

⇒ 

" PoFS " 

⇒ 

" P 4 " 

⇒ 

" P20 " 

⇒ 

" Id " 

⇒ 

" FACt 

⇒ 

" I n t "  while mode key press repeated.

Each item setting methodes are refer to next pages.

Save

  :

 If you complete your setting in the each 

mode, Press ENTER once to save and exit to 
measure mode. 

Off level

P

On level

On level

Off level

P

P

PK

S1

S2

P

PK

S1

S2

P

PK

PK

S1

S2

P

Summary of Contents for SIT Series

Page 1: ...R Copyright ⓒ 2003 08 ULFA TECHNOLOGY CO LTD http www ulfatech com 1 Instruction Manual Digital Differential Pressure Switch Transmitter 1 General Specification 2 Installation 3 Wiring 4 Function 5 Setting Calibration 4 Digit Display 4 20mA Output 2 Level Control ...

Page 2: ...C 50 60Hz Connections 2 screw terminal block Display 4 Digit LED Warm up Time 15 minutes SWITCH Relay Contact 2 SPDT NC COM NO Contact Rating 1A 30VDC 0 5A 125VAC Connections 6 Screw terminal block Level setting Individual level setting Switch 1 2 TRANSMITTER SIT Range Table Connections 2 Screw terminal block Output Signal 4 20mADC limited at 30mADC Model No Range Resolution Loop Resistance 0 1100...

Page 3: ...he power specification is DC24V or AC220V 2 Verify that the facility s main power source is turned off or disconnected 3 Connect lead cable to power terminal matching polarity as shown in FIG 2 below Take care that wrong wiring will damage the Instrument and malfunction AC220V is not concerned to polarity CURRENT OUT CONNECTION 4 20mA SIT only The SIT sends a standard 2 wire 4 20mA current out 1 C...

Page 4: ...sent by RS232 or RS485 for option specification ID setting This mode set identification number for communication Over pressure warning SIT SDS displays warning on segment for over pressure positive and negative Upper 4 elements of 7segment blink for warning when measurement pressure over 10 for high pressure factory setting value And under 4 elements of 7segment _ _ _ _ blink for warning when meas...

Page 5: ...to measure mode Press ENTER for more than 3 seconds to save and exist in the switch level setting mode SWITCH2 OFF LEVEL Switch level setting Press MODE key to select sw2 off level set mode S2 LED is on while into the sw2 off level setting mode 2oFF displayed like left while press mode key in the sw2 off level setting mode Set your switch level use up down key Press ENTER once to save and exit to ...

Page 6: ...sure 20 times for 2 seconds and calculate average of measured 20 data to display and 4 20mA current output This functions is useful to measure hunted pressure Press MODE key for more than 3 seconds till sw1 LED is on and appear Int on segment display like left Release MODE key then appear current set time on segment display default set time is 0 5 sec Set your sampling time use up down key Press E...

Page 7: ...zero span etc Press MODE key for more than 3 seconds till appear Int on segment display Press MODE key once till appear FACt on segment display Press ENTER once to recall and exit to measure mode Press ENTER key for more than 3 seconds till appear SAvE on segm ent to recall and exist in the setting mode ID No setting ID number is use for address for communication to master It s concern to SIT SDS ...

Reviews: