SIT/SDS Series

                                         

DIGITAL DIFFERENTIAL PRESSURE SWITCH & TRANSMITTER

Copyright 

ⓒ 

2003.08  ULFA  TECHNOLOGY  CO.,LTD                                                    http://www.ulfatech.com

6

   

User setting mode

Zero setting

Press ENTER for more than 3 seconds to save and 
exist in the setting mode.

Release User setting mode :

 

Press ENTER once to save and exit to measure 
mode.
If you are not operate this instrument for about 1 
minute, It's released  user setting mode automatically 
and return to measuring mode.

Optimize zero to display and current out automatically 

by front key pressed.

CAUTION : Release pressure port free before
                      zero  set

Press MODE for more 
than 3 seconds till  sw1 
LED is on and appear 
"Int" on segment display

Press MODE key once 
till appear "PoFS" on 
segment.

Press ENTER once to 
set zero and exit to 
measure mode. "PoFS" 
 

blink for about 5

seconds to calculate 
zero.
Press ENTER key for 
more than 5 seconds till 
appear "SAvE" on 
segment to save and 
exist in the setting mode.

Sampling time setting

It can be set 0.1~5.0 seconds by 0.1 sec resolution. 
SIT/SDS reading pressure 0.1sec interval for a 
setting time and calculate average pressure to 
display and 4-20mA output.

(ex) setting time : 2 sec
   SIT/SDS reading pressure 20 times for 2 seconds 
   and calculate average of measured 20 data to 
   display  and 4-20mA current output.

This functions is useful to measure hunted pressure

Press MODE key for 
more than 3 seconds till 
sw1 LED is on and 
appear "Int" on segment 
display like left.

Release MODE key then 
appear current set time 
on segment display 
(default set time is 0.5 
sec)

Set your sampling time 
use up/down key

Press ENTER once to 
save and exit to measure 
mode. 

Press ENTER key for 
more than 3 seconds till 
appear "SAvE" on 
segment to save and 
exist in the sampling time 
setting mode

4mA current setting(SIT)

This function is set pressure level to 4mA current out. 
Generally pressure zero is setting to 4mA current out.
By the way, negative pressure is setting in another 
case. SIT/SDS can be set any pressure level to  4mA 
current out between low and high pressure range.
Low and high pressure ranges are setting in factory.  

Press MODE key for 
more than 3 seconds till 
appear "Int" on segment 
display.

Press MODE key once 
till appear "P4" on 
segment.

Set your pressure level 
to 4mA out use up/down 
key 

Press ENTER once to 
save and exit to measure 
mode. 

Press ENTER key for 
more than 3 seconds till 
appear "SAvE" on segm 
-ent to save and exist in 
the setting mode

                       

         

                       
         
                                 

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PK

S1

S2

P

PK

S1

S2

P

PK

S1

S2

P

PK

S1

S2

P

PK

S1

S2

P

PK

S1

S2

P

PK

S1

S2

Summary of Contents for SIT Series

Page 1: ...R Copyright ⓒ 2003 08 ULFA TECHNOLOGY CO LTD http www ulfatech com 1 Instruction Manual Digital Differential Pressure Switch Transmitter 1 General Specification 2 Installation 3 Wiring 4 Function 5 Setting Calibration 4 Digit Display 4 20mA Output 2 Level Control ...

Page 2: ...C 50 60Hz Connections 2 screw terminal block Display 4 Digit LED Warm up Time 15 minutes SWITCH Relay Contact 2 SPDT NC COM NO Contact Rating 1A 30VDC 0 5A 125VAC Connections 6 Screw terminal block Level setting Individual level setting Switch 1 2 TRANSMITTER SIT Range Table Connections 2 Screw terminal block Output Signal 4 20mADC limited at 30mADC Model No Range Resolution Loop Resistance 0 1100...

Page 3: ...he power specification is DC24V or AC220V 2 Verify that the facility s main power source is turned off or disconnected 3 Connect lead cable to power terminal matching polarity as shown in FIG 2 below Take care that wrong wiring will damage the Instrument and malfunction AC220V is not concerned to polarity CURRENT OUT CONNECTION 4 20mA SIT only The SIT sends a standard 2 wire 4 20mA current out 1 C...

Page 4: ...sent by RS232 or RS485 for option specification ID setting This mode set identification number for communication Over pressure warning SIT SDS displays warning on segment for over pressure positive and negative Upper 4 elements of 7segment blink for warning when measurement pressure over 10 for high pressure factory setting value And under 4 elements of 7segment _ _ _ _ blink for warning when meas...

Page 5: ...to measure mode Press ENTER for more than 3 seconds to save and exist in the switch level setting mode SWITCH2 OFF LEVEL Switch level setting Press MODE key to select sw2 off level set mode S2 LED is on while into the sw2 off level setting mode 2oFF displayed like left while press mode key in the sw2 off level setting mode Set your switch level use up down key Press ENTER once to save and exit to ...

Page 6: ...sure 20 times for 2 seconds and calculate average of measured 20 data to display and 4 20mA current output This functions is useful to measure hunted pressure Press MODE key for more than 3 seconds till sw1 LED is on and appear Int on segment display like left Release MODE key then appear current set time on segment display default set time is 0 5 sec Set your sampling time use up down key Press E...

Page 7: ...zero span etc Press MODE key for more than 3 seconds till appear Int on segment display Press MODE key once till appear FACt on segment display Press ENTER once to recall and exit to measure mode Press ENTER key for more than 3 seconds till appear SAvE on segm ent to recall and exist in the setting mode ID No setting ID number is use for address for communication to master It s concern to SIT SDS ...

Reviews: