SIT/SDS Series

                                         

DIGITAL DIFFERENTIAL PRESSURE SWITCH & TRANSMITTER

Copyright 

ⓒ 

2003.08  ULFA  TECHNOLOGY  CO.,LTD                                                    http://www.ulfatech.com

7

   

20mA current setting(SIT)

Recall to Factory setting value

This function is set pressure level to 20mA current 
out, That is set span. SIT/SDS can be set any 
pressure level to  20mA current out between low 
and high pressure ranges.
Low and high pressure ranges are setting in factory. 

Press MODE key for 
more than 3 seconds till 
appear "Int" on segment 
display.

Press MODE key once 
till appear "P20" on 
segment display.

Set your pressure level 
to 20mA current out use 
up/down key 

Press ENTER once to 
save and exit to measure 
mode. 

Press ENTER key for 
more than 3 seconds till 
appear "SAvE" on segm 
-ent to save and exist in 
the setting mode

This function is recall to initial states of factory 
out from unmatched user parameters that zero, 
span etc.

Press MODE key for 
more than 3 seconds till 
appear "Int" on segment 
display.

Press MODE key once 
till appear "FACt" on 
segment display.

Press ENTER once to 
recall and exit to measure 
mode. 

Press ENTER key for 
more than 3 seconds till 
appear "SAvE" on segm 
-ent to recall and exist in 
the setting mode

ID No setting

ID number is use for address for communication to 
master. It's concern to SIT/SDS communication function 
installed.(option)

Press MODE key for 
more than 3 seconds till 
appear "Int" on segment 
display.

Press MODE key once 
till appear "ID" on 
segment.

Set your ID No use 
up/down key(0~255)
default set is 0.

Press ENTER once to 
save and exit to measure 
mode. 

Press ENTER key for 
more than 3 seconds till 
appear "SAvE" on segm 
-ent to save and exist in 
the setting mode.

ULFA TECHNOLOGY CO.,LTD

344, industrial zone ,201 haan 3-dong

kwang myung-city, kyung ki-do

423-754 KOREA

TEL:02-806-4403 FAX:02-806-4406

[email protected]

                       
         
                                 

                       
                                 

                       
         
                                 

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PEAK

P

PK

S1

S2

P

PK

PK

S1

S2

P

PK

S1

S2

P

PK

S1

S2

P

PK

S1

S2

S1

S2

P

P

Summary of Contents for SIT Series

Page 1: ...R Copyright ⓒ 2003 08 ULFA TECHNOLOGY CO LTD http www ulfatech com 1 Instruction Manual Digital Differential Pressure Switch Transmitter 1 General Specification 2 Installation 3 Wiring 4 Function 5 Setting Calibration 4 Digit Display 4 20mA Output 2 Level Control ...

Page 2: ...C 50 60Hz Connections 2 screw terminal block Display 4 Digit LED Warm up Time 15 minutes SWITCH Relay Contact 2 SPDT NC COM NO Contact Rating 1A 30VDC 0 5A 125VAC Connections 6 Screw terminal block Level setting Individual level setting Switch 1 2 TRANSMITTER SIT Range Table Connections 2 Screw terminal block Output Signal 4 20mADC limited at 30mADC Model No Range Resolution Loop Resistance 0 1100...

Page 3: ...he power specification is DC24V or AC220V 2 Verify that the facility s main power source is turned off or disconnected 3 Connect lead cable to power terminal matching polarity as shown in FIG 2 below Take care that wrong wiring will damage the Instrument and malfunction AC220V is not concerned to polarity CURRENT OUT CONNECTION 4 20mA SIT only The SIT sends a standard 2 wire 4 20mA current out 1 C...

Page 4: ...sent by RS232 or RS485 for option specification ID setting This mode set identification number for communication Over pressure warning SIT SDS displays warning on segment for over pressure positive and negative Upper 4 elements of 7segment blink for warning when measurement pressure over 10 for high pressure factory setting value And under 4 elements of 7segment _ _ _ _ blink for warning when meas...

Page 5: ...to measure mode Press ENTER for more than 3 seconds to save and exist in the switch level setting mode SWITCH2 OFF LEVEL Switch level setting Press MODE key to select sw2 off level set mode S2 LED is on while into the sw2 off level setting mode 2oFF displayed like left while press mode key in the sw2 off level setting mode Set your switch level use up down key Press ENTER once to save and exit to ...

Page 6: ...sure 20 times for 2 seconds and calculate average of measured 20 data to display and 4 20mA current output This functions is useful to measure hunted pressure Press MODE key for more than 3 seconds till sw1 LED is on and appear Int on segment display like left Release MODE key then appear current set time on segment display default set time is 0 5 sec Set your sampling time use up down key Press E...

Page 7: ...zero span etc Press MODE key for more than 3 seconds till appear Int on segment display Press MODE key once till appear FACt on segment display Press ENTER once to recall and exit to measure mode Press ENTER key for more than 3 seconds till appear SAvE on segm ent to recall and exist in the setting mode ID No setting ID number is use for address for communication to master It s concern to SIT SDS ...

Reviews: