FRENCH WARNING TRANSLATIONS CONT.

5

To prevent electrostatic discharge, wipe down 

cover and enclosure of any dust build-up before 

removing cover. 

Pour éviter les décharges électrostatiques, nettoyez le capot 

et le boîtier de toute accumulation de poussière avant de 

retirer le capot.

5

Disconnect all supply circuits before wiring device. 

Wire device in accordance with local and national 

electrical codes. Maximum recommended wire size 

and recommended tightening torque for field wir

-

ing terminal blocks are shown within table 3 (page 

xx). 

Débrancher tous les circuits d’alimentation avant de 

brancher l’appareil. Le câblage doit être effectuée selon 

les codes électriques nationaux et locaux. Tailles de fils 

recommandées maximales et couples de serrage pour le 

terrain câblage des borniers sont  indiqués dans le tableau 3 

(la page xx).

5

To prevent seizure of enclosure cover, do not re-

move lubricant. Threads should also be free of dirt 

and other contaminants. 

Pour éviter le grippage du couvercle du boîtier, ne pas en-

liever le lubrifiant. Les fils doivent également être exempts 

de saleté et d’autres contaminants.

5

To prevent ignition, disconnect power before 

removing enclosure cover. Keep cover tight while 

in operation. Do not disconnect equipment unless 

power has been switched off or the area is known 

to non-hazardous.

Pour éviter l’inflammation, couper l’alimentation avant 

de retirer le couvercle du boîtier. Maintenir le couvercle 

fermé pendant le fonctionnement. Ne pas déconnecter 

l’équipement que lorsque l’alimentation est coupée ou que 

la zone est connue pour être non explosives.

5

Do not replace components unless power has been 

switched off or the area is known to be non-hazard-

ous.

Ne remplacez pas les composants avant que le courant soit 

coupé ou que la zone est connue pour être non explosives.

5

The devices shall be properly grounded in the end 

use application using the ground screws provided 

with the enclosure. 

Les appareils doivent être correctement mis à la terre en 

utilisant les vis de terre fournies avec l’enceinte.

5

Field wiring must be rated 105°C minimum. For 

ambient temperatures below -10°C, use suitable 

field wiring.

Câblage sur le terrain doit être évalué à 105°C minimum. 

Pour une température ambiante inférieure à -10°C, utiliser 

le câblage approprié.

5

Models 1XSWLL and 1XSWHL derive their 

power directly from a PLC/DCS discrete input or 

other low-current DC loads (see Figure 4-5, page 

xx). The switched output maximum load rating is 

0.1A. The device must not be connected directly 

to a power supply without an appropriate current 

limiting load such as that provided by a PLC/DCS 

discrete input. Overloading the switch may cause 

failure (see Table 2).

Les modèles 1XSWLL et 1XSWHL sont directement 

alimentés par une entrée logique PLC / DCS ou par une 

autre charge continue à faible courant (voir la figure 4-5, 

page xx). La charge nominale maximale de la sortie com-

mutée est de 0,1 A. L'appareil ne doit pas être connecté 

directement à une source d'alimentation sans une charge de 

limitation de courant appropriée telle que celle fournie par 

une entrée TOR PLC / DCS. Une surcharge du commuta-

teur peut provoquer une panne (voir le tableau 2).

8

Do not connect model 1XSWLL directly to a 

power supply without a suitable load in series with 

the switch.

Ne connectez pas le modèle 1XSWLL directement à une 

source d'alimentation sans charge appropriée en série avec 

le commutateur.

8

Substitution of components may impair intrinsic 

safety.

La substitution de composants peut nuire à la sécurité 

intrinsèque.

12

Use of this option may create a condition where 

the display may indicate “0.00” when significant 

pressure or temperature (up to 10% of maximum 

range) exists in the system. Independent verifica

-

tion of the process variable should be done prior to 

maintenance on the system when “offset” appears 

on the display.

L'utilisation de cette option peut créer une condition dans 

laquelle l'écran peut indiquer «0,00» lorsqu'une pression 

ou une température significative (jusqu'à 10% de la plage 

maximale) existe dans le système. Une vérification in

-

dépendante de la variable de processus doit être effectuée 

avant la maintenance du système lorsque «offset» apparaît 

à l'écran.

Summary of Contents for 1XSWHH

Page 1: ...Ex UL 08 0017X Applicable Standards UL 913 UL 60079 0 UL 60079 11 CSA C22 2 No 157 92 CSA C22 2 No 60079 0 11 CSA C22 2 No 60079 11 14 EN 60079 0 2012 A11 2013 EN 60079 11 2012 IEC 60079 0 Ed 6 2011 06 Corr 1 2012 01 Corr 2 2013 12 IEC 60079 11 Ed 2011 Suitable for appropri ate use in EXIA Intrinsically Safe Sécurité Intrin séque Class I Div 1 Groups A B C D Class II Div 1 Groups E F G Class III C...

Page 2: ... cover cemented joint 0 753 19 1 mm rabbet spigot minimum length Breather element threaded joint M8 1 25 6g 6H medium fit class 11 threads engaged minimum Electrical conduit threaded joint 3 4 14 NPT 5 threads engaged minimum Enclosure to sensor threaded joint Pressure models 1 20 UNEF 2 10 threads engaged minimum Temperature models 1 2 14 NPT 5 threads engaged minimum Remote and local spring load...

Page 3: ... 1 A maximum I Am Working IAW The One Series also contains UE s patented IAW self diagnostic software On a continuous basis the IAW algorithm checks for proper opera tion and locally reports the status using messages or revolving arrows on the display For remote reporting a discrete IAW Output signal can be monitored by the control system and used to detect normal tripped and fault conditions IAW ...

Page 4: ...NEVER INSERT ANY OBJECT INTO THE PRESSURE SENSOR OPENING DAMAGE TO THE SENSOR WILL RESULT AFFECTING ACCURACY Pressure and Differential Pressure Models To pipe mount Thread the pressure connection onto the pressure port with thread sealant making sure that the mating threads are clean and free of debris Use a wrench on the pressure connection hex to tighten Test for leaks On Differential Pressure m...

Page 5: ...S SHOULD ALSO BE FREE OF DIRT AND OTHER CONTAMINANTS Remove the enclosure cover by turning it counter clockwise for 7 revolutions Figure 2 Carefully remove the display module by grasping the outer edge and pulling it away from the base enclosure Figure 3 being careful not to strain any of the wired connections Allow the display module to hang from the wired connections to access the base enclosure...

Page 6: ...LL 1XSWLL 1XSWHL 1XSWHL WIRING DIAGRAMS Models 1XSWLL and 1XSWHL Maximum Switch Ratings Flameproof and Non Incendive Model Signal Name Voltage Rating Current Rating 1XSWLL SW 7 8 50 0 VDC 0 1 amperes1 IAW 7 8 50 0 VDC 0 1 amperes1 1XSWHL SW 70 240 VAC VDC 0 1 amperes1 IAW 7 8 50 0 VDC 0 1 amperes1 1XSWHH SW 70 240 VAC 0 150 10 amperes2 IAW 7 8 50 0 VDC 0 1 amperes1 1 Derate at 0 001 amperes per C ...

Page 7: ...N Connections for the programmable solid state relay switch are made at TB2 terminals A and B refer to table 2 page 6 and table 3 page 8 The wiring diagram below Figure 9 provides a view inside the One Series base enclosure with the display module removed TB2 is located there All models include a separate IAWTM switched output located at TB3 on the back of the display module This signal provides t...

Page 8: ...ty parameters and wiring information https www ueonline com support product drawings Model 1XSWLL must be wired to an approved I S galvanically isolated barrier for Zone 0 EPL Ga and Class I Division 1 classifications The information provided is for reference only and is intended to act as a guide in the selection of a suitable I S Barrier SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY Ins...

Page 9: ...utton sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR MAX MIN or MAN RSET if Latch is set will appear on the display This is the first command prompt in the Programming Mode NOTE The One Series will automatically exit the Programming Mode and resume monitoring the process go back online if two minutes elap...

Page 10: ...ne break The IAW output always operates in DTT mode Please use the Switch Decision Logic Figure 11 page 11 for help with setting the appropriate switch mode Press and release the left 2 button until the desired mode appears Press the right g button to select the mode and move on to the set point SP will appear NOTE The set point is the process value at which the One Series opens or closes the swit...

Page 11: ...m temperature Example The P15 sensor has a range of 0 to 300 psi When setting a Set Point of 150 the actual switch point may occur between 148 5 and 151 5 due to the accuracy error of 1 5 300 x 0 5 Switch Decision Logic Figure 11 Resetting the Maximum Minimum Values The One Series continuously captures the readings from the sensor and stores one minimum and maximum value since the last time they w...

Page 12: ...actory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to enter the new offset and return to the main menu Adjusting Span SPAN provides an adjustment to shift the slope of the sensor s response curve to accommodate an offset value other than zero To adjust SPAN calculate and enter a new SPAN valu...

Page 13: ...he process port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are programmable If the process variable does not change by the amount and selected time period the display will indicate PLUG and the IAW Output will open indicating a fault Refer to the Programming Flowchart on page 18 Enter the Programming Mode and press the left 2...

Page 14: ...le selections are as follows Pressure Models OFF Default Temperature Models 1 2 second 1 4 second 1 second 1 2 second 2 seconds 1 second 2 seconds Using the left 2 button select a time constant Press the right g button to enter the time constant and return to main menu NOTE The One Series typically responds to a process value change in less that 100 milliseconds when the Filter is set to off Using...

Page 15: ...tibility of the One Series with your PLC DCS or relay we can help Please have the manu facturer s model number ready when you call us In rare cases when the series resistor value is too large and falls out of the Acceptable Range placing another resistor across the input will allow it to work Please call 1 617 923 6977 Inside Sales for assistance 0 2000 4000 6000 8000 10000 12000 14000 16000 18000...

Page 16: ...r connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagnostic Fault Relay Monitor The relay output fault monitor circuit has detected that the output state of the solid state relay is incorrect This feature must be enabled in the menu Check the wiring connections or dis able...

Page 17: ...6977 or go online at www UEonline com UUC to obtain a unique unlock code The Kanban number from the product nameplate is required see Figure 13 THIS DOCUMENT IS PROPRIETARY PROPERTY OF UNITED ELECTRIC CONTROLS UNAUTHORIZED USE IS STRICTLY PROHIBITED TOLERANCES ON FRACTIONS 1 64 1 2 0 010 0 005 2 PLACE DEC 3 PLACE DEC ANGLES Page 1 of 1 WARNING AGENCY CRITICAL DOCUMENT NO REVISIONS WITHOUT CERTIFIC...

Page 18: ...e flash Err OPEN FALL CLOSE RISE CLOSE FALL OPEN OUT OF WINDOW CLOSE OUT OF WINDOW SPH DBH SPL DBL Note Enter Set Point High Dead Band High Set Point Low and Dead Band Low Details of entry are similar above OFST POS NEG Offset out of Range Flash Err 8888 Set Blinking Digit Increments of Blinking Digit Sets Digit and moves to the next SPAN POS NEG SPAN out of Range Flash Err 8888 Set Blinking Digit...

Page 19: ...PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 264 16 mm 203 2 mm 137 16 mm 129 54 mm 134 62 mm 137 16 mm 76 2 mm 92 20 mm 129 54 mm 134 62 mm 137 16 mm 107 95 mm 61 91 mm 158 75 mm 7 11 mm 107 95 mm 76 2 mm 6 35 mm 8 73 mm DIMENSIONAL DRAWINGS GAGE P...

Page 20: ...ATED CABLE Ø0 125 3 18 mm FOR DC UNITS Ø0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT PIPE NIPPLE 300 SERIES st st 0 50 12 7 mm Temperature Sensors Remote TR1 TRC TH1 THC TC1 TCC SENSOR OPTIONS Spring Loaded Local TTC Fixed Local TL1 TL3 Differential Pressure 1 4 18 NPT MALE BOTH END...

Page 21: ... minimes Orienter l unité d une manière à empêcher l humidité de pénétrer dans l enceinte Utiliser des raccords d étanchéité bien notés pour l entrée de fil électrique Ne pas monter l unité à des températures ambiantes dépassant les limites publiées Cela est particulièrement important pour les unités de température à montage locale L utilisation envelopper est recommandée lorsque le soleil et la p...

Page 22: ...s à la terre en utilisant les vis de terre fournies avec l enceinte 5 Field wiring must be rated 105 C minimum For ambient temperatures below 10 C use suitable field wiring Câblage sur le terrain doit être évalué à 105 C minimum Pour une température ambiante inférieure à 10 C utiliser le câblage approprié 5 Models 1XSWLL and 1XSWHL derive their power directly from a PLC DCS discrete input or other...

Page 23: ...el Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national electrical codes using wire size recommended in installa tion sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery f...

Reviews: