GENERAL

MISUSE OF THIS PRODUCT MAY CAUSE EXPLOSION AND PERSONAL INJURY.  THESE INSTRUCTIONS MUST BE THOROUGHLY READ AND UNDERSTOOD 

BEFORE UNIT IS INSTALLED.  SEE THE PRODUCT NAMEPLATE INFORMATION FOR SPECIFIC AGENCY CERTIFICATIONS APPLICABLE TO YOUR PRODUCT.

SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN HAZARDOUS LOCATIONS.  CABLE GLANDS USED MUST BE RATED FOR A MINIMUM 

OF IP66 IN ORDER TO MAINTAIN THE SAME IP RATING.

FOR ZONE HAZARDOUS LOCATIONS, ALL CABLE ENTRY DEVICES SHALL BE CERTIFIED IN TYPE OF EXPLOSION PROTECTION FLAMEPROOF ENCLOSURE “d” 

WITH AN IP66 RATING, SUITABLE FOR THE CONDITIONS OF USE AND CORRECTLY INSTALLED.  IF CABLES AND CABLE GLANDS ARE NOT USED, A STOPPING 

BOX SHALL BE PROVIDED WITHIN 2” OF THE ENCLOSURE.  FLAMEPROOF JOINT AND GAP DETAILS ARE PROVIDED ON PAGE 2. 

INSTALL UNITS WHERE SHOCK, VIBRATION AND TEMPERATURE FLUCTUATIONS ARE MINIMAL. ORIENT UNIT TO PREVENT MOISTURE FROM ENTERING 

ENCLOSURE. USE PROPERLY RATED SEALING FITTINGS FOR ELECTRICAL WIRE ENTRY. DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING 

PUBLISHED LIMITS. THIS IS ESPECIALLY CRITICAL FOR LOCAL MOUNT TEMPERATURE UNITS. USE OF A SHROUD IS RECOMMENDED WHERE DIRECT SUNLIGHT 

AND RAIN MAY COME IN CONTACT WITH THE ENCLOSURE.

DURING INSTALLATION, MARK THE BOX NEXT TO EACH PROTECTION METHOD ON THE NAMEPLATE THAT APPLIES TO YOUR APPLICATION.
THIS EQUIPMENT IS CERTIFIED IN ACCORDANCE WITH THE REQUIREMENTS OF THE FOLLOWING APPLICABLE STANDARDS (SEE TABLE 1) AND 

IS SUITABLE FOR USE IN NON-HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS, AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR 

APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS. 

N. America

Europe

International

Intrinsic Safety - Model 1XSWLL Only

Cert number:

UL File E226592

DEMKO 09 ATEX 0813748X

IECEx UL 08.0017X

Applicable Standards  UL 913, UL-60079-0, UL 60079-11, CSA C22.2 No. 

157-92, CSA C22.2 No. 60079-0:11, CSA C22.2 No. 
60079-11:14

EN 60079-0:2012 + A11:2013
EN 60079-11:2012

IEC 60079-0:Ed.6(2011-06) + 
Corr.1 (2012-01) + Corr.2 (2013-
12)
IEC 60079-11:Ed.2011

Suitable for appropri-
ate use in:
EXIA Intrinsically 
Safe - Sécurité Intrin-
séque

Class I, Div. 1, Groups A, B, C & D
Class II, Div. 1 Groups E, F & G 
Class III
Class I, Zone 0 AEx ia IIC T4
Ex ia IIC T4

II 1 G Ex ia IIC T4 Ga
II 1 D Ex ia IIIC T135°C Da
-40°C < TAMB < +85°C

Ex ia IIC T4 Ga
Ex ia IIIC T135°C Da
-40°C < TAMB < +85°C

Flameproof - Models 1XSWLL, 1XSWHL and 1XSWHH

Cert Number:

UL File E226592

DEMKO 09 ATEX 0813748X

IECEx UL 08.0017X

Applicable Standards UL 1203, UL 60079-0, UL 60079-1, UL 61010-1, UL 

50, UL 50E, CSA C22.2 No. 25, CSA C22.2 No. 30, CSA 
C22.2 No. 60079-0:11, CSA C22.2 No. 60079-1:11, CSA 
C22.2 No. 61010-1-12, CSA C22.2 No. 94.01-07, CSA 
C22.2 No. 94.2-07

EN 60079-0:2012 + A11:2013
EN 60079-1:2014
EN 60079-31:2014

IEC 60079-0:Ed.6(2011-06) + 
Corr.1 (2012-01) + Corr.2 (2013-
12)
IEC 60079-1:Ed.7
IEC 60079-31:Ed.2

Suitable for appropri-
ate use in:

Class I, Div. 1, Groups A, B, C & D
Class II, Div. 1 Groups E, F & G
Class III
Class I, Zone 1 AEx db IIC T5 (1XSWLL)
Class I, Zone 1 Ex db IIC T5
Class I, Zone 1 AEx db IIC T3/T5 (1XSWHL & 1XSWHH)

II 2 G Ex db IIC T3/T5 Gb
II 2 D Ex tb IIIC T90°C Db
IP66
-40°C ≤ TAMB ≤ +85°C (1XSWLL)
-40°C ≤ TAMB ≤ +80°C (1XSWHL & 
1XSWHH)

Ex db IIC T3/T5 Gb
Ex tb IIIC T90°C Db
IP66
-40°C ≤ TAMB ≤ +85°C (1XSWLL)
-40°C ≤ TAMB ≤ +80°C (1XSWHL 
& 1XSWHH)

One Series 

Electronic Pressure, Differential 

Pressure and Temperature Switches

Discrete Input, Intrinsically Safe, 

Flameproof and Non-Incendive

Models:  1XSWLL, 1XSWHL, and 1XSWHH

U N I T E D   E L E C T R I C 

C O N T R O L S

Installation and Maintenance 

Instructions

IM_1XSW-02

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended 
Practices, Liabilities and Warranties.  All Warnings are translated to French and can be found on pages 21 and 22.

Summary of Contents for 1XSWHH

Page 1: ...Ex UL 08 0017X Applicable Standards UL 913 UL 60079 0 UL 60079 11 CSA C22 2 No 157 92 CSA C22 2 No 60079 0 11 CSA C22 2 No 60079 11 14 EN 60079 0 2012 A11 2013 EN 60079 11 2012 IEC 60079 0 Ed 6 2011 06 Corr 1 2012 01 Corr 2 2013 12 IEC 60079 11 Ed 2011 Suitable for appropri ate use in EXIA Intrinsically Safe Sécurité Intrin séque Class I Div 1 Groups A B C D Class II Div 1 Groups E F G Class III C...

Page 2: ... cover cemented joint 0 753 19 1 mm rabbet spigot minimum length Breather element threaded joint M8 1 25 6g 6H medium fit class 11 threads engaged minimum Electrical conduit threaded joint 3 4 14 NPT 5 threads engaged minimum Enclosure to sensor threaded joint Pressure models 1 20 UNEF 2 10 threads engaged minimum Temperature models 1 2 14 NPT 5 threads engaged minimum Remote and local spring load...

Page 3: ... 1 A maximum I Am Working IAW The One Series also contains UE s patented IAW self diagnostic software On a continuous basis the IAW algorithm checks for proper opera tion and locally reports the status using messages or revolving arrows on the display For remote reporting a discrete IAW Output signal can be monitored by the control system and used to detect normal tripped and fault conditions IAW ...

Page 4: ...NEVER INSERT ANY OBJECT INTO THE PRESSURE SENSOR OPENING DAMAGE TO THE SENSOR WILL RESULT AFFECTING ACCURACY Pressure and Differential Pressure Models To pipe mount Thread the pressure connection onto the pressure port with thread sealant making sure that the mating threads are clean and free of debris Use a wrench on the pressure connection hex to tighten Test for leaks On Differential Pressure m...

Page 5: ...S SHOULD ALSO BE FREE OF DIRT AND OTHER CONTAMINANTS Remove the enclosure cover by turning it counter clockwise for 7 revolutions Figure 2 Carefully remove the display module by grasping the outer edge and pulling it away from the base enclosure Figure 3 being careful not to strain any of the wired connections Allow the display module to hang from the wired connections to access the base enclosure...

Page 6: ...LL 1XSWLL 1XSWHL 1XSWHL WIRING DIAGRAMS Models 1XSWLL and 1XSWHL Maximum Switch Ratings Flameproof and Non Incendive Model Signal Name Voltage Rating Current Rating 1XSWLL SW 7 8 50 0 VDC 0 1 amperes1 IAW 7 8 50 0 VDC 0 1 amperes1 1XSWHL SW 70 240 VAC VDC 0 1 amperes1 IAW 7 8 50 0 VDC 0 1 amperes1 1XSWHH SW 70 240 VAC 0 150 10 amperes2 IAW 7 8 50 0 VDC 0 1 amperes1 1 Derate at 0 001 amperes per C ...

Page 7: ...N Connections for the programmable solid state relay switch are made at TB2 terminals A and B refer to table 2 page 6 and table 3 page 8 The wiring diagram below Figure 9 provides a view inside the One Series base enclosure with the display module removed TB2 is located there All models include a separate IAWTM switched output located at TB3 on the back of the display module This signal provides t...

Page 8: ...ty parameters and wiring information https www ueonline com support product drawings Model 1XSWLL must be wired to an approved I S galvanically isolated barrier for Zone 0 EPL Ga and Class I Division 1 classifications The information provided is for reference only and is intended to act as a guide in the selection of a suitable I S Barrier SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY Ins...

Page 9: ...utton sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR MAX MIN or MAN RSET if Latch is set will appear on the display This is the first command prompt in the Programming Mode NOTE The One Series will automatically exit the Programming Mode and resume monitoring the process go back online if two minutes elap...

Page 10: ...ne break The IAW output always operates in DTT mode Please use the Switch Decision Logic Figure 11 page 11 for help with setting the appropriate switch mode Press and release the left 2 button until the desired mode appears Press the right g button to select the mode and move on to the set point SP will appear NOTE The set point is the process value at which the One Series opens or closes the swit...

Page 11: ...m temperature Example The P15 sensor has a range of 0 to 300 psi When setting a Set Point of 150 the actual switch point may occur between 148 5 and 151 5 due to the accuracy error of 1 5 300 x 0 5 Switch Decision Logic Figure 11 Resetting the Maximum Minimum Values The One Series continuously captures the readings from the sensor and stores one minimum and maximum value since the last time they w...

Page 12: ...actory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to enter the new offset and return to the main menu Adjusting Span SPAN provides an adjustment to shift the slope of the sensor s response curve to accommodate an offset value other than zero To adjust SPAN calculate and enter a new SPAN valu...

Page 13: ...he process port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are programmable If the process variable does not change by the amount and selected time period the display will indicate PLUG and the IAW Output will open indicating a fault Refer to the Programming Flowchart on page 18 Enter the Programming Mode and press the left 2...

Page 14: ...le selections are as follows Pressure Models OFF Default Temperature Models 1 2 second 1 4 second 1 second 1 2 second 2 seconds 1 second 2 seconds Using the left 2 button select a time constant Press the right g button to enter the time constant and return to main menu NOTE The One Series typically responds to a process value change in less that 100 milliseconds when the Filter is set to off Using...

Page 15: ...tibility of the One Series with your PLC DCS or relay we can help Please have the manu facturer s model number ready when you call us In rare cases when the series resistor value is too large and falls out of the Acceptable Range placing another resistor across the input will allow it to work Please call 1 617 923 6977 Inside Sales for assistance 0 2000 4000 6000 8000 10000 12000 14000 16000 18000...

Page 16: ...r connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagnostic Fault Relay Monitor The relay output fault monitor circuit has detected that the output state of the solid state relay is incorrect This feature must be enabled in the menu Check the wiring connections or dis able...

Page 17: ...6977 or go online at www UEonline com UUC to obtain a unique unlock code The Kanban number from the product nameplate is required see Figure 13 THIS DOCUMENT IS PROPRIETARY PROPERTY OF UNITED ELECTRIC CONTROLS UNAUTHORIZED USE IS STRICTLY PROHIBITED TOLERANCES ON FRACTIONS 1 64 1 2 0 010 0 005 2 PLACE DEC 3 PLACE DEC ANGLES Page 1 of 1 WARNING AGENCY CRITICAL DOCUMENT NO REVISIONS WITHOUT CERTIFIC...

Page 18: ...e flash Err OPEN FALL CLOSE RISE CLOSE FALL OPEN OUT OF WINDOW CLOSE OUT OF WINDOW SPH DBH SPL DBL Note Enter Set Point High Dead Band High Set Point Low and Dead Band Low Details of entry are similar above OFST POS NEG Offset out of Range Flash Err 8888 Set Blinking Digit Increments of Blinking Digit Sets Digit and moves to the next SPAN POS NEG SPAN out of Range Flash Err 8888 Set Blinking Digit...

Page 19: ...PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 264 16 mm 203 2 mm 137 16 mm 129 54 mm 134 62 mm 137 16 mm 76 2 mm 92 20 mm 129 54 mm 134 62 mm 137 16 mm 107 95 mm 61 91 mm 158 75 mm 7 11 mm 107 95 mm 76 2 mm 6 35 mm 8 73 mm DIMENSIONAL DRAWINGS GAGE P...

Page 20: ...ATED CABLE Ø0 125 3 18 mm FOR DC UNITS Ø0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT PIPE NIPPLE 300 SERIES st st 0 50 12 7 mm Temperature Sensors Remote TR1 TRC TH1 THC TC1 TCC SENSOR OPTIONS Spring Loaded Local TTC Fixed Local TL1 TL3 Differential Pressure 1 4 18 NPT MALE BOTH END...

Page 21: ... minimes Orienter l unité d une manière à empêcher l humidité de pénétrer dans l enceinte Utiliser des raccords d étanchéité bien notés pour l entrée de fil électrique Ne pas monter l unité à des températures ambiantes dépassant les limites publiées Cela est particulièrement important pour les unités de température à montage locale L utilisation envelopper est recommandée lorsque le soleil et la p...

Page 22: ...s à la terre en utilisant les vis de terre fournies avec l enceinte 5 Field wiring must be rated 105 C minimum For ambient temperatures below 10 C use suitable field wiring Câblage sur le terrain doit être évalué à 105 C minimum Pour une température ambiante inférieure à 10 C utiliser le câblage approprié 5 Models 1XSWLL and 1XSWHL derive their power directly from a PLC DCS discrete input or other...

Page 23: ...el Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national electrical codes using wire size recommended in installa tion sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery f...

Reviews: