3.3 Exploded view of appliance

The appliance shown above is a left-hand version: in the case of a right-hand version, the connector of the preheater, bypass valve and the siphon 
connector are installed in mirror image!

1

Touchscreen

12

Heat exchanger

2

USB connector (X13)

13

Motor bypass valve

3

Service connector

14

Exhaust air fi lter

4

LED indicator

15

Bypass valve

5

Maximum protection preheater

16

Power cable 230 volt

6

Preheater

17

Relay output (X19)

7

Temperature sensor

18

24 volt connector (X18)

8

Supply fi lter

19

eBus connector (X17)

9

Exhaust fan

20

24 volt connector (X16)

10

Siphon

21

Modbus/ externalbus connector (X15)

11

Supply ventilator

22

Multiple switch connector (X14)

4 Operation

4.1 Description

The appliance is supplied ready for plugging in and works automatically according to the standard settings. The 
discharged dirty indoor air warms up the fresh clean outdoor air. That saves energy while fresh air is supplied to 
the desired rooms.

The control system has four ventilation modes. The air fl ow rate can be adjusted for each ventilation mode. The 
constant volume control system ensures that the ventilation balance between the supply and exhaust fan is realized 
independent of the duct pressure.

If no external control is connected on to the appliance, then the appropriate ventilation model can be chosen on 
the touchscreen display.

For external control a 4-way switch (  Connecting extra multiple switch with fi lter indication page 37) can, for 
example, be chosen, but control is also possible with the Air Control (  Connecting Air Control page 42), CO

2

 sensor(s) 

(  Connecting CO₂ sensor(s) page 43), a humidity sensor (  Connecting humidity sensor page 45) or the App.

4.2 Bypass

The 100% bypass makes it possible to supply outside air, which is not heated up by the heat exchanger. Particularly 
during summer nights it is desirable to supply cooler outside air. The warm air in the dwelling is then replaced as 
much as possible by cooler outside air.

The bypass valve opens and closes automatically when a number of conditions are met (see table below for bypass 
conditions).

Follow step numbers 2.1 to 2.6 in the settings menu in the user interface (  Setting values standard appliance 
page 52) in order to adjust the operation of the bypass valve.

Bypassvalve open

|

The outdoor temperature is higher than 10°C (adjustable between 7°C and 15°C at step no. 2.3) 

and

|

the outdoor temperature is lower than the indoor temperature of the dwelling 

and

|

the temperature from the dwelling is higher than 24°C (adjustable between 15°C and 35°C at step no. 2.2)

Bypassvalve closed

|

The outdoor temperature is lower than 10°C (adjustable between 7°C and 15°C at step no. 2.3) C 

or

|

the outdoor temperature is higher than the indoor temperature of the dwelling 

or

|

the temperature from the dwelling is lower than the set temperature at step no. 2.2 in the settings menu minus 
the set temperature at the hysteresis (step no. 2.4).

Bypass valve preconditions

The appliance features a ‘Bypass boost’ function. This means that when this function is switched on (can be switched at 
step 2.5) the ventilation mode with an opened bypass valve goes to maximum air fl ow rate (adjustable at step no. 2.6).

Summary of Contents for Ubiflux Vigor W225

Page 1: ...INSTALLATION REGULATIONS Ubiflux Vigor W225 English...

Page 2: ...ave received clear instructions on the safe use of the appliance and understand the possible dangers on the condition that the appliance has been placed and installed in the normal position for use Ch...

Page 3: ...Maintenance siphon 31 9 3 Maintenance installer 32 10 Electrical diagram 35 11 Electrical connections accessories 37 11 1 Connecting position switch 37 11 1 1 Connecting position switch with filter in...

Page 4: ...dimensions It is possible however to later equip the appliance with a Plus pcb The appliance comes ready to plug in with a 230 V mains plug 3 Version 3 1 Technical information Ubiflux Vigor W225 Plus...

Page 5: ...a right hand version the warm connections 1 3 are on the right hand side of the appliance Left hand version Right hand version All dimensions in millimeters Diameter of all collars is 125 mm All dimen...

Page 6: ...r example be chosen but control is also possible with the Air Control Connecting Air Control page 42 CO2 sensor s Connecting CO sensor s page 43 a humidity sensor Connecting humidity sensor page 45 or...

Page 7: ...ions regarding the ventilation of homes and residential Safety provisions for low voltage installations The regulations for connecting indoor plumbing in homes and residential buildings Any additional...

Page 8: ...2 not supplied with the appliance so that the siphon can be cleaned easily in the future The condensate discharge can be connected for example with a straight or angled connection with gasket Slide th...

Page 9: ...of 5 m s in the main ducts and 3 5 m s in the branches The location of the discharge of the mechanical ventilation air and the sewer stack vent must be chosen to prevent noise nuisance The location of...

Page 10: ...building management system Using the red 3 pole connector X15 or with the Plus version the red connector X06 on the UWA2 E pcb a connection can be made between the appliance and the ModBus system Ele...

Page 11: ...sed to operate the appliance and to provide the user with information about the status of the appliance When the mains power is switched on the software version is first shown the main screen is then...

Page 12: ...emand driven ventilation Break contact active or make contact active This appliance is set as Master appliance if a number of appliances are connected cascade Appliance is set as Slave appliance maxim...

Page 13: ...e to reset the correct language time and date in setting menu 4 The appliance will then operate immediately after this according to the mode of the multiple switch If no multiple switch is connected t...

Page 14: ...y Codes Non locking fault When the appliance detects a non locking fault it will keep running limitedly The permanently lighted display shows the fault symbol Press the fault symbol for an explanation...

Page 15: ...available Take voltage from appliance Replace UWA2 B pcb Fault is automatically reset when voltage is again put back on appliance E1155 E2000 Touchscreen fault general fault message Fault codes only...

Page 16: ...Home button and the display then returns to the main screen the filter message is reset and the filter message now disappears Comment If the filter wizard is opened in order to replace the filter whil...

Page 17: ...supply by pulling out the plug Open the filter door 2 Remove the two filters 3 Remove the front cover 4 Remove the heat exchanger Be careful not to damage the foam parts in the appliance 5 Wash the h...

Page 18: ...y back into the appliance when doing so take care that the EPS parts and rails in the appliance are not damaged which could otherwise leads to internal leaks in the appliance Take care when returning...

Page 19: ...ervice activities then a wizard starts up automatically follow the instructions on the display for the correct connection of the fan cables Basic print X15 externalBus ModBus X16 24V X17 eBus X18 24V...

Page 20: ...or wireless remote control C Transmitter with 4 settings for example kitchen D Transmitter with 2 settings for example bathroom E Any additional 2 or 4 settings transmitters maximum of 6 transmitters...

Page 21: ...on the type of modular cable used 11 1 4 Connecting extra multiple switch with filter indication A Ubiflux Vigor appliance For example a Ubiflux Vigor appliance type 4 0 B1 Multiple switch with filte...

Page 22: ...ector E Position green eBus connector to rear of control 1 Ubiflux Vigor appliance 2 Basis pcb 3 Cover 4 The cable that comes with RH cable 5 RH humidity sensor 6 Duct from dwelling A Ubiflux Vigor ap...

Page 23: ...ir quality Matching the ventilation need with demand driven ventilation can be done in two different ways namely based on CO2 measurements or based on a time program Two different sets are available f...

Page 24: ...ppliance 4 Temperature sensor 5 PCB type UVP1 6 Airflow direction 7 Dipswitch setting postheater 1 Heating coil 2 Maximum safety with manual reset 3 2 pole eBus connection X17 on appliance 4 Temperatu...

Page 25: ...g on and off Off On off 11 2 Switch temperature 1 5 C 0 0 C 10 0 C 11 3 Switch temperature 2 25 C 15 0 C 40 0 C 11 4 Mode valve 10 volt control Closed Open Closed 11 5 Valve control Relay output 1 Rel...

Page 26: ...pcb UWA2 E 0883246 9 Mains plug and cable 230 V 0883261 10 Internal preheater incl maximum security 11 Temperature sensor NTC 10K 0704637 12 Condensation discharge 0883264 13 Cable set 0883265 14 Cab...

Page 27: ...pass temperature from outside 10 C 7 C 15 C 2 4 Bypass hysteresis 2 C 0 C 5 C 2 5 Mode Bypass boost Uit Aan Uit 2 6 Fan setting selection Bypass boost 3 0 1 2 of 3 3 Frost protection 3 1 Frost tempera...

Page 28: ...iance with Plus pcb Step no Description Factory settings Setting range Comment 9 Switch contacts 9 1 Make or break contact 1 Make Make Break 9 2 Switch contact control 1 Off Off On Meets Bypass condit...

Page 29: ...e valve 24 volt control Closed Open Dicht 11 5 Valve control Relay output 1 Relay output 1 Relay output 2 Analogue output 1 Analogue output 2 14 Conformity declaration Conformity declaration Manufactu...

Page 30: ...heat exchanger Recuperative plastic cross counterflow heat exchanger Thermal efficiency 92 Maximum flow rate 225 m h Maximum rated power 165 W Sound power level Lwa 39 dB A Reference flow rate 158 m h...

Page 31: ...ng Sustainable materials are used in the manufacture of this appliance The packaging should be disposed of in a responsible manner and in accordance with governmental regulations 60 Art nr 616711 A Ub...

Page 32: ...Jan Samijnstraat 9 B 9050 Gentbrugge Tel 32 0 9 237 11 00 www ubbink be info ubbink be Ubbink UK Ltd Unit 2 Redbourne Park Liliput Road Brackmills Ind Est Northampton NN4 7DT T 44 0 1604 433000 F 44 0...

Reviews: