Possible 

ERP

 (External Error) Values:

Display

Status

Recommended Corrective Actions

Err 1

Temperature Sensor Fault

Temperature sensor failure, wire harness loose or shorted connection or control 

hardware failure:

-   Check sensor is securely attached to boiler control

-   Check that sensor wire is not damaged

-   If secure and in good condition, replace sensor

-   If problem persists, replace control

Err 2

Communication Fault

Enviracom terminal is shorted to ground or line voltage. 

-  Check wiring to EnviraCOM terminals 1,2 and 3.  Wiring to external EnviraCom 

   device is incorrect.

Err 3

Internal Hardware Fault

Error detected with AC power supply frequency or boiler control failure.  Cycle power to 

the control. Replace control if problem persists.  

Err 4

Burner Output (B1) Fault

B1 output sensed powered during safety output relay check sequence or un-powered 

during running, or powered in idle in combination with water temperature above 264°F 

limit. Cycle power to the control. Replace control if problem persists.

Err 5

Line Voltage Fault (< 80 Vac) AC voltage out of specification high or low; check L1, L2, 110 VAC. 

Err 6

Fuse missing

Internal fuse is blown or missing. The fuse protects the Aquastat from miss wiring  the 

L1 and L2 on Oil Primary.  When the Oil Primary is correctly wired the fuse is useless 

and not detected. If Primary is wired incorrectly the fuse is blown out and Aquastat 

report error 6.  EnviraCOM message is sent when the wiring is fixed and the error 

disappears to indicate the end of the error state. Check wiring and replace fuse.  

Err 7

User settings lost, (reset to 

factory defaults)

Warning: Generated if user adjustments are lost and the device uses factory default 

values.  Error is cleared by entering and exiting the Adjustment mode.  Replace control 

if problem persists.  

Err 8

Manual Reset Lockout 

(resettable)

Set if 

Err 4

 was invoked four times in a row. Check wiring and clear Lockout by 

pressing all three user keys for 30 seconds.

xIII.  TROUBLE  SHOOTING (continued)

E.

  USE BOILER CONTROL DISPLAY 

ERR

 AND 

ERP

 NUMBERS TO DIRECT TROUBLESHOOTING

 

If the Boiler Control detects an error it will flash "

Err

" (boiler control error) or "

ErP

" (external error) followed by a number.  

Use this text and number to identify the boiler problem and corrective action in the table below.  If there is no error display 

proceed to Paragraph E: 

TABLE 14A:  BOILER CONTROL ERROR NUMBERS

make sure that they are tight.  Also, check the wiring 

on the boiler against the wiring diagram in Figures 

28A, 28B and 28C.  Ensure that incoming 120 Vac 

power polarity is correct and that the boiler is properly 

grounded. 

4.  A defective control or component is generally the least 

likely cause.  Before replacing a component, try to rule 

out all other possible causes.

5.  When checking voltage across wiring harness pins 

be careful not to insert the meter probes into the pins.  

Doing so may damage the pin, resulting in a loose 

connection when the harness is reconnected.

ErP

Value Description

4

Warning, Cad Cell Resistance High (Service Required)

5

No Ignition, Check Cad Cell

9

Warning, Flame Proven, Late in Trial

10

No Ignition, Check Ignition Transformer

18

Internal Error, Electronics Failure

20

No Ignition

21

No Ignition, After Flame Loss During Run

22

Flame Lost During Run Three Times In A Row

23

Flame Out of Sequence, During Pre-Purge

24

Flame Out of Sequence, During Post-Purge

25

Oil Primary Lockout, Manual Reset Required

ErP

Value Description

34

Cad Ohms Permanently Low (Flame Out of Sequence)

35

Duplicate Zone

58

AC Line Frequency Error

59

AC Line Voltage Error

84

Low Water Event

89

Communication Lost

91

Communication Error

119

Sensor Failure

140

Low Probe Signal

141

Manual Reset Lockout

Possible 

ERP

 (External Error) Values (continued):

Summary of Contents for MPO-IQ

Page 1: ...n on boiler provide Boiler Model Number and Serial Number as shown on Rating Label Boiler Model Number MPO IQ Boiler Serial Number Installation Date Heating Contractor Phone Number Address As an ENERG...

Page 2: ...oke and unburned fuel to pass out of the combustion chamber and clog the flueways of the boiler 8 COLD OIL If the oil temperature approaching the fuel pump is 40 F or lower poor combustion or delayed...

Page 3: ...osed Note The Safety Monitoring Circuit SMC is designed to provide lockout in the event of a stuck or welded motor relay C IQ OIL BOILER CONTROL When a problem occurs with the boiler operation the IQ...

Page 4: ...ce control if problem persists Err 8 Manual Reset Lockout resettable Set if Err 4 was invoked four times in a row Check wiring and clear Lockout by pressing all three user keys for 30 seconds XIII TRO...

Page 5: ...uel supply lines and filter for obstructions ErP 10 No Ignition Check Ignition Transformer The burner was not lit and spark was not detected Check the electrodes spring contacts or high voltage wires...

Page 6: ...iring ErP 84 LWCO Option Card Low Water Event Low water level Limit has caused the boiler to shutdown Make sure that the water level has reached the probe Limit will re close automatically after water...

Page 7: ...Water DHW Priority Forcing Circulator Off When there is a DHW heat request wired to the boiler control s ZR terminal the System Circulator will be forced off for the duration of the DHW heat request...

Page 8: ...heck fuel lines and filter are free of obstructions Check fuel lines are fully purged of air Use the pump priming feature to purge the system of air Check that the burner motor is spinning and the pum...

Page 9: ...install card If problem persists replace card Err 5 Limit Output OFF in ON State Check limit string wiring replace the Option Panel Err 6 Incorrect Wiring Check boiler wiring Err 7 Internal Option Pan...

Reviews: