7
TABLE 1A: DIMENSIONAL
DA
TA
(SEE FIGURE 1)
TABLE 1B: RA
TING DA
TA
Boiler Model
No.
Dimensions See Figure 1
W
ater Content - Gallons
Heat T
ransfer
Surface Area
- Sq. Ft.
Actual Shipping
W
eight (LB.)
“A”
“B”
“C”
MPO-IQ84
16-5/8”
24”
5”
7.70
13.29
430
MPO-IQ1
15
16-5/8”
24”
5”
7.70
13.29
430
MPO-IQ147
22-5/8”
24”
6”
11.08
20.29
545
MPO-IQ189
28-5/8”
30”
6”
14.46
27.29
658
MPO-IQ231
34-5/8”
36”
7”
17.84
34.29
771
NOTE: 1. Maximum W
orking Pressure: W
ater: 30 PSI Shipped From Factory (Standard),
40 PSI Optional, 50 PSI Optional
Boiler
Model No.
Burner Capacity
NET
AHRI
Ratings
AFUE %
Minimum Chimney
Requirements
Direct V
ent System
GPH
MBH
DOE Heating Capacity MBH
W
ater MBH
W
ater
Boiler
Round In. Dia.
Rectangle
In. x In.
Height
Ft.
Model
Vent
Connector Dia. Inch
MPO-IQ84
0.60
84
74
64
87
6
8 x 8
15
N/A
N/A
MPO-IQ1
15
0.82
11
5
101
87
87
6
8 x 8
15
N/A
N/A
MPO-IQ147
1.05
147
129
11
2
87
6
8 x 8
15
FDVS-56
5
MPO-IQI89
1.35
189
167
145
87
7
8 x 8
15
FDVS-56
5
MPO-IQ231
1.65
231
203
177
87
7
8 x 8
15
FDVS-67
6
Summary of Contents for MPO - IQ
Page 6: ...6 Figure 1 MPO IQ84 Thru MPO IQ231 Water Boiler ...
Page 22: ...22 Figure 11 Boiler Removal from Skid III UNIT PAK BOILER ASSEMBLY TRIM CONTROLS continued ...
Page 42: ...42 Figure 28A Schematic Wiring Diagram VII ELECTRICAL continued ...
Page 43: ...43 Figure 28B Schematic Wiring Diagram Burner Options VII ELECTRICAL continued ...
Page 44: ...44 Figure 28C Ladder Diagram VII ELECTRICAL continued ...
Page 70: ...70 Bare Boiler Assembly XIV Repair Parts continued ...
Page 72: ...72 Jacket Assembly XIV Repair Parts continued ...
Page 74: ...74 MPO IQ84 Thru MPO IQ231 Water Boilers Trim and Controls XIV Repair Parts continued ...
Page 78: ...78 Beckett AFG Burner XIV Repair Parts continued ...
Page 80: ...80 Beckett NX Burner XIV Repair Parts continued ...
Page 92: ...92 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...