2. POSITION ThE BOILER
WARNINGS
1.
Slide the boiler into desired location.
2.
Meet the minimum clearances to
combustible construction per the
Specification
Section of this manual.
3.
Allow 24" service clearance in front and on
the left side of the boiler.
OBSERVE MINIMUM CLEARANCES to
combustible walls and ceilings to avoid potential
fire hazard.
DO NOT INSTALL ON CARPET
. This may cause
a fire.
INSTALLING THE BOILER NEAR A SOURCE OF
FLAMMABLE LIQUIDS
or gases may cause fire or
explosion.
CLEAN BURNERS DAILY if operating the boiler in
a dusty environment.
PROTECT IGNITION SYSTEM COMPONENTS
from sources of water that may spray, drip, or rain
on them during installation or service.
4.
Level the boiler, using shims as necessary.
5.
Assure that the front air dam (applicable to
5-section thru 9-section boilers only) is in
place and undamaged. See Figure 2-a.
2-a
WARNING
Models ES25, ES26, ES27, ES28 and ES29 only. Verify Front Air Dam is installed and undamaged
(Figure 2-a). A missing or damaged Front Air Dam will negatively affect the performance of this boiler,
which can cause serious property damage, personal injury or death.
NOTE: Front Air Dam not used on Models ES23 and ES24.